System Description
Senscient ELDS™
Rev 15
19
GB
2.6.4 Thermal Window for Cross-Duct Units
In order to allow ELDS Cross Duct units to be mounted upon ducts which may temporarily reach
internal temperatures that are higher than the maximum upper service temperature for which
ELDS systems are certified (+60ºC), a mounting arrangement which includes a thermal window is
available. This arrangement insulates an ELDS unit’s lens-window from hot gases inside the duct,
allowing ELDS XD units to continue being used provided that air temperatures outside of the duct
are within the certified range.
Provided that there is adequate ventilation; and any in-duct temperature excursion is not of too
long a duration (≤ 15 minutes), it should be possible to mount and operate XD ELDS units on
ducts where air / gas temperatures inside the duct of up to 120ºC are temporarily present. Longer
term operation at high duct temperatures, or operation in conditions of restricted ventilation would
require measurement of the temperatures that the XD ELDS units become exposed to - in order to
ensure that the maximum certified operating temperature of +60ºC is not exceeded.
2.7. SITE Installation & Maintenance Software
SITE (Senscient Installation and Test Environment) is a software application provided by
Senscient to enable the installation, commissioning and testing of all types of ELDS OPGD
products; and is supplied pre-installed on ATEX or CSA (UL) certified industrial computers. Due to
the complexity of the computing and communications technologies employed by SITE, Senscient
can only provide support to users that are running SITE on factory tested and approved platforms.
SITE is capable of communicating with ELDS units either over RS485 or Bluetooth™ * wireless
communications links. The RS485 connection is made via a USB:RS485 adaptor included as part
of the installation kit. The Bluetooth™ connection is built into the industrial computer and is factory
activated and configured for use with SITE and ELDS units. More detailed information and
guidance with respect to the type of communication link to use when working with ELDS units is
provided in sections 4.5 to 4.7.
*All ELDS units can be commissioned using the RS485 communications link, regardless of their
type or age. From November 2011 onwards, Bluetooth™ communications were added alongside
RS485 with the introduction of Mod State 1, open-path, ELDS units. (The Mod State of ELDS units
can be found on the certification / serial number label on the terminal compartment cover.)
The necessary steps to commission a system using SITE are outlined in section 4.5 and some key
maintenance and problem solving guidance is provided in section 7.2. The following sections here
provide an overview of SITE itself.
Содержание Senscient ELDS 1000 series
Страница 1: ...Operating Manual Senscient ELDS 1000 2000 Series Open Path Cross Duct Gas Detectors A 5170 0 Rev 15 ...
Страница 58: ...Installation Commissioning 58 Senscient ELDS Rev 15 GB 2 x Mounting Brackets ...
Страница 140: ...Certification 140 Senscient ELDS Rev 15 GB 9 1 2 Control Drawing CENELEC ATEX ...
Страница 142: ...Certification 142 Senscient ELDS Rev 15 GB 9 1 4 Control Drawing CSA US Canada ...
Страница 158: ...Appendix D Manufacturer s EC Declarations 158 Senscient ELDS Rev 15 GB 13 Appendix D Manufacturer s EC Declarations ...
Страница 159: ...Appendix D Manufacturer s EC Declarations Senscient ELDS Rev 15 159 GB ...
Страница 160: ...Appendix D Manufacturer s EC Declarations 160 Senscient ELDS Rev 15 GB ...
Страница 184: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose ...