System Description
26
Senscient ELDS™
Rev 15
GB
2.7.6 Config
This button provides access to configuration information and to processes that allow the
configuration to be changed once a unit has been installed.
A new screen is presented with a range of options as illustrated below:
The screen is arranged with several ‘tabs’ or pages of information and in addition up to 3 context
sensitive buttons at the bottom. The ‘tabs’ displayed will depend on the unit (Tx or Rx) and also on
the connection type. The example here is for a Receiver. A Transmitter will not include the
“Zero Unit”, or “4-20mA Configuration” options but will include a “SimuGas” option.
Info
This tab contains key information regarding the unit including the unit identity, firmware release
and configuration. In addition it provides access to three configurable items relating to Bluetooth
access, the control of the window heaters on the unit and the behaviour of Beam-Block in the
presence of gas.
Bluetooth Enabled/Disabled indicates if Bluetooth communication is currently facilitated on the
unit. By default all ELDS units are shipped with Bluetooth communication active, however some
customers may choose to inhibit this communication protocol for security reasons. The Bluetooth
support can be disabled or enabled as appropriate by checking the associated checkbox. In the
example above the Bluetooth is currently active so unchecking this checkbox will immediately
disable the Bluetooth connectivity in the unit. Note that access to this feature is restricted by
password access (see section 2.7.8 below). More details of how to disable Bluetooth are provided
in section 4.5.3 below.
Desert Mode is a feature to allow the control of the window-heaters on the ELDS unit to be
changed such that they are likely to be ‘off’ for a majority of the time in hot environments. This will
ensure that the power consumption and internal temperature of the ELDS unit will be minimised
and ensure the longest possible life of the internal components. It is recommended that the
“Desert” feature be enabled on units deployed in hot environments where daytime temperature is
likely to routinely exceed 25°C.
Содержание Senscient ELDS 1000 series
Страница 1: ...Operating Manual Senscient ELDS 1000 2000 Series Open Path Cross Duct Gas Detectors A 5170 0 Rev 15 ...
Страница 58: ...Installation Commissioning 58 Senscient ELDS Rev 15 GB 2 x Mounting Brackets ...
Страница 140: ...Certification 140 Senscient ELDS Rev 15 GB 9 1 2 Control Drawing CENELEC ATEX ...
Страница 142: ...Certification 142 Senscient ELDS Rev 15 GB 9 1 4 Control Drawing CSA US Canada ...
Страница 158: ...Appendix D Manufacturer s EC Declarations 158 Senscient ELDS Rev 15 GB 13 Appendix D Manufacturer s EC Declarations ...
Страница 159: ...Appendix D Manufacturer s EC Declarations Senscient ELDS Rev 15 159 GB ...
Страница 160: ...Appendix D Manufacturer s EC Declarations 160 Senscient ELDS Rev 15 GB ...
Страница 184: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose ...