Appendix F – MODBUS Communications
Senscient ELDS™
Rev 15
171
GB
Input
Applies
Content
Comment
21
Rx
Last SG Month
1 to 12
22
Rx
Last SG Day
1 to 31
23
Rx
Last SG Hour
0 to 23
24
Rx
Last SG Minute
0 to 59
25
Rx
Last SG Second
0 to 59
26
Rx
No. Good SimuGas
Per laser, for a dual laser system a single
SG process will normally produce
+2 counts for No. Good
27
Rx
No. Bad SimuGas
28
Rx
L0 Last Gas Value
ppm.m
29
Rx
L1 Last Gas Value
ppm.m
30
Rx
L0 Last Gas Year
Base 2000
31
Rx
L0 Last Gas Month
1 to 12
32
Rx
L0 Last Gas Day
1 to 31
33
Rx
L0 Last Gas Hour
0 to 23
34
Rx
L0 Last Gas Minute
0 to 59
35
Rx
L0 Last Gas Second
0 to 59
36
Rx
L1 Last Gas Year
Base 2000
37
Rx
L1 Last Gas Month
1 to 12
38
Rx
L1 Last Gas Day
1 to 31
39
Rx
L1 Last Gas Hour
0 to 23
40
Rx
L1 Last Gas Minute
0 to 59
41
Rx
L1 Last Gas Second
0 to 59
These are read only and can be read using the Modbus command 0x04 (Read Input Registers).
There are two separate outputs of the measured gas values for the Receiver units. The ‘simple’
form (Inputs 1 and 2) contain the gas value in ppm.m units. These outputs are restricted to the
range 0 to 65535 ppm.m which is sufficient to cover the normal full scale range of most ELDS
variants. The second form of output is used to duplicate the gas results (Inputs 16 to 19) as well as
providing the signal level for each laser (Inputs 12 to 15). For these each output is coded using two
registers, the actual value is then formed using the product of both registers divided by a scaling
factor of 1000. This allows a much greater dynamic range for these outputs (good accuracy is
maintained for values from 0.1 to 4×106. These then greatly extend the quality of output of the gas
results as well as providing a full diagnostic measure of the signal level for each laser.
Содержание Senscient ELDS 1000 series
Страница 1: ...Operating Manual Senscient ELDS 1000 2000 Series Open Path Cross Duct Gas Detectors A 5170 0 Rev 15 ...
Страница 58: ...Installation Commissioning 58 Senscient ELDS Rev 15 GB 2 x Mounting Brackets ...
Страница 140: ...Certification 140 Senscient ELDS Rev 15 GB 9 1 2 Control Drawing CENELEC ATEX ...
Страница 142: ...Certification 142 Senscient ELDS Rev 15 GB 9 1 4 Control Drawing CSA US Canada ...
Страница 158: ...Appendix D Manufacturer s EC Declarations 158 Senscient ELDS Rev 15 GB 13 Appendix D Manufacturer s EC Declarations ...
Страница 159: ...Appendix D Manufacturer s EC Declarations Senscient ELDS Rev 15 159 GB ...
Страница 160: ...Appendix D Manufacturer s EC Declarations 160 Senscient ELDS Rev 15 GB ...
Страница 184: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose ...