Appendix E – HART Communications
164
Senscient ELDS™
Rev 15
GB
14.3. Details of ELDS Data Available via HART
The HART communications modem incorporated into ELDS Receivers supports all Universal
HART Commands as defined in HCF_SPEC-127, Revision 7.1, except Command 6.
At the time of writing, Common Practice and Device Specific HART commands are not supported
and there is no HART capability in ELDS Tx units.
The most useful information available by way of HART from an ELDS system includes the
following:-
Gas Measurements (‘Burdens’)
– ELDS systems measure gas ‘burdens’, which are effectively
the integrated concentration of the target gas along the whole of the monitored optical path. The
gas ‘burden’ for each output is mapped to the HART primary and secondary variables.
Although the 4-20mA output range is inherently limited by the maximum current that can be
output (typically 21.5mA), the values passed to the HART primary and secondary variables
are not restricted, allowing the user to monitor gas levels that are beyond the 4-20mA
output / measurement ‘range’ of the instrument.
Analogue 4-20mA(1) Level
– The analogue current that is to be output by 4-20mA(1) output of an
ELDS Receiver can be obtained using the appropriate universal HART command.
Last SimuGas Event
– Information regarding the last detected Simu-Gas event is made available
in the Tag/Descriptor/Date fields (HART command 13) and the Tertiary (tv) and Quaternary (qv)
variables. Values are in ppm.m units irrespective of the range/output of the primary and secondary
variables. The unit will have 0.0 for each of these values on power-up.
Serial Number and TAG
– The unit serial number and current user TAG is made available
through the HART interface, with it being possible to change the user TAG via HART if required.
Содержание Senscient ELDS 1000 series
Страница 1: ...Operating Manual Senscient ELDS 1000 2000 Series Open Path Cross Duct Gas Detectors A 5170 0 Rev 15 ...
Страница 58: ...Installation Commissioning 58 Senscient ELDS Rev 15 GB 2 x Mounting Brackets ...
Страница 140: ...Certification 140 Senscient ELDS Rev 15 GB 9 1 2 Control Drawing CENELEC ATEX ...
Страница 142: ...Certification 142 Senscient ELDS Rev 15 GB 9 1 4 Control Drawing CSA US Canada ...
Страница 158: ...Appendix D Manufacturer s EC Declarations 158 Senscient ELDS Rev 15 GB 13 Appendix D Manufacturer s EC Declarations ...
Страница 159: ...Appendix D Manufacturer s EC Declarations Senscient ELDS Rev 15 159 GB ...
Страница 160: ...Appendix D Manufacturer s EC Declarations 160 Senscient ELDS Rev 15 GB ...
Страница 184: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose ...