17. Appendix H – 4-20mA Current Output Ranges
ELDS Receiver units contain two 4-20mA current loops that are used to signal gas levels. For dual
gas units each loop is used for an individual gas, however for single gas units the second output
loop will provide an alternative measurement of the gas that may be of a different full scale to the
primary output. The table below details this for each ELDS part number.
Part No.
Description
4-20mA Full Scale Range
Certification
1
2
L-1012-3
1LFL.m CH
4
ATEX Long Range
1 LEL.m
1 LEL.m
ATEX/BASEEFA
L-1012-4
1LFL.m CH
4
CSA Long Range
1 LEL.m
1 LEL.m
CSA/UL
L-1012-5
1LFL.m CH
4
GOST-R Long Range
1 LEL.m
1 LEL.m
GOST-R
L-1012-6
1LFL.m CH
4
GOST-K Long Range
1 LEL.m
1 LEL.m
GOST-K
L-1012-7
1LFL.m CH
4
InMetro Long Range
1 LEL.m
1 LEL.m
InMetro
L-1015-3
5LFL.m CH
4
ATEX Long Range
5 LEL.m
1 LEL.m
ATEX/BASEEFA
L-1015-4
5LFL.m CH
4
CSA Long Range
5 LEL.m
1 LEL.m
CSA/UL
L-1015-5
5LFL.m CH
4
GOST-R Long Range
5 LEL.m
1 LEL.m
GOST-R
L-1015-6
5LFL.m CH
4
GOST-K Long Range
5 LEL.m
1 LEL.m
GOST-K
L-1015-7
5LFL.m CH
4
InMetro Long Range
5 LEL.m
1 LEL.m
InMetro
L-1092-3
1LFL.m Ethylene ATEX Long Range
1 LEL.m
1 LEL.m
ATEX/BASEEFA
L-1092-4
1LFL.m Ethylene CSA Long Range
1 LEL.m
1 LEL.m
CSA/UL
L-1092-5
1LFL.m Ethylene GOST-R Long Range
1 LEL.m
1 LEL.m
GOST-R
L-1092-7
1LFL.m Ethylene InMetro Long Range
1 LEL.m
1 LEL.m
InMetro
M-1009-3 1LFL.m / 1000ppm.m CH
4
ATEX Medium Range
1 LEL.m
1000 ppm.m
ATEX/BASEEFA
M-1009-4 1LFL.m / 1000ppm.m CH
4
CSA Medium Range
1 LEL.m
1000 ppm.m
CSA/UL
M-1009-5 1LFL.m / 1000ppm.m CH
4
GOST-R Medium Range 1 LEL.m
1000 ppm.m
GOST-R
M-1009-6 1LFL.m / 1000ppm.m CH
4
GOST-K Medium Range 1 LEL.m
1000 ppm.m
GOST-K
M-1009-7 1LEL.m / 1000ppm.m CH
4
InMetro Medium Range 1 LEL.m
1000 ppm.m
InMetro
M-1010-3 1000ppm.m CH
4
ATEX Medium Range
1000 ppm.m
1 LEL.m
ATEX/BASEEFA
M-1010-4 1000ppm.m CH
4
CSA Medium Range
1000 ppm.m
1 LEL.m
CSA/UL
M-1010-5 1000ppm.m CH
4
GOST-R Medium Range
1000 ppm.m
1 LEL.m
GOST-R
M-1010-6 1000ppm.m CH
4
GOST-K Medium Range
1000 ppm.m
1 LEL.m
GOST-K
M-1010-7 1000ppm.m CH
4
InMetro Medium Range
1000 ppm.m
1 LEL.m
InMetro
M-1012-3 1LFL.m CH
4
ATEX Medium Range
1 LEL.m
1 LEL.m
ATEX/BASEEFA
M-1012-4 1LFL.m CH
4
CSA Medium Range
1 LEL.m
1 LEL.m
CSA/UL
M-1012-5 1LFL.m CH
4
GOST-R Medium Range
1 LEL.m
1 LEL.m
GOST-R
M-1012-6 1LFL.m CH
4
GOST-K Medium Range
1 LEL.m
1 LEL.m
GOST-K
M-1012-7 1LFL.m CH
4
InMetro Medium Range
1 LEL.m
1 LEL.m
InMetro
M-1015-3 5LFL.m CH
4
ATEX Medium Range
5 LEL.m
1 LEL.m
ATEX/BASEEFA
M-1015-4 5LEL.m CH
4
CSA Medium Range
5 LEL.m
1 LEL.m
CSA/UL
M-1015-5 5LFL.m CH
4
GOST-R Medium Range
5 LEL.m
1 LEL.m
GOST-R
M-1015-6 5LFL.m CH
4
GOST-K Medium Range
5 LEL.m
1 LEL.m
GOST-K
M-1015-7 5LFL.m CH
4
InMetro Medium Range
5 LEL.m
1 LEL.m
InMetro
M-1051-3 50ppm.m HF ATEX Medium Range
50 ppm.m
100 ppm.m
ATEX/BASEEFA
M-1051-4 50ppm.m / 100ppm.m HF CSA Medium Range
50 ppm.m
100 ppm.m
CSA/UL
M-1052-4 200ppm.m / 100ppm.m HF CSA Medium Range
200ppm.m
100 ppm.m
CSA/UL
M-1054-3 1000ppm.m HF ATEX Medium Range
1000 ppm.m
500 ppm.m
ATEX/BASEEFA
M-1054-4 1000ppm.m HF CSA Medium Range
1000 ppm.m
500 ppm.m
CSA/UL
Содержание Senscient ELDS 1000 series
Страница 1: ...Operating Manual Senscient ELDS 1000 2000 Series Open Path Cross Duct Gas Detectors A 5170 0 Rev 15 ...
Страница 58: ...Installation Commissioning 58 Senscient ELDS Rev 15 GB 2 x Mounting Brackets ...
Страница 140: ...Certification 140 Senscient ELDS Rev 15 GB 9 1 2 Control Drawing CENELEC ATEX ...
Страница 142: ...Certification 142 Senscient ELDS Rev 15 GB 9 1 4 Control Drawing CSA US Canada ...
Страница 158: ...Appendix D Manufacturer s EC Declarations 158 Senscient ELDS Rev 15 GB 13 Appendix D Manufacturer s EC Declarations ...
Страница 159: ...Appendix D Manufacturer s EC Declarations Senscient ELDS Rev 15 159 GB ...
Страница 160: ...Appendix D Manufacturer s EC Declarations 160 Senscient ELDS Rev 15 GB ...
Страница 184: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose ...