Problem Solving
120
Senscient ELDS™
Rev 15
GB
Modbus or HART Communications are Less Reliable than Anticipated
Problems with achieving reliable, long term communications using either the HART or Modbus
communications protocols are encountered from time to time. These problems are not a
consequence of there being anything wrong with an ELDS OPGD. If HART or Modbus
communications difficulties are experienced, the most likely explanation is that electrical
interference on the field cabling is causing data corruption.
The firmware responsible for handling HART and Modbus communications on an ELDS unit
includes routines that detect interference or corruption; and that attempt to handle such
problems. However, in instances where a lasting breakdown of HART or Modbus
communications develops, the simplest way of resolving this problem may be cycling the power
to the system, or to the ELDS unit with which communications have broken down.
7.2. SITE Diagnostics Screen
In many instances, the quickest and simplest way of identifying and diagnosing a problem with an
ELDS system will be by reviewing the contents of the SITE Test/Diagnostics Screen. Select the
Test / Diagnostics screen by clicking on the corresponding button in the Main SITE screen.
The SITE Test / Diagnostics screen provides the operator with a great deal of information about
the status of the ELDS Transmitter or Receiver (or both) with which SITE is communicating. The
information provided by the SITE Diagnostics Screen is described in the following sub-sections:
Содержание Senscient ELDS 1000 series
Страница 1: ...Operating Manual Senscient ELDS 1000 2000 Series Open Path Cross Duct Gas Detectors A 5170 0 Rev 15 ...
Страница 58: ...Installation Commissioning 58 Senscient ELDS Rev 15 GB 2 x Mounting Brackets ...
Страница 140: ...Certification 140 Senscient ELDS Rev 15 GB 9 1 2 Control Drawing CENELEC ATEX ...
Страница 142: ...Certification 142 Senscient ELDS Rev 15 GB 9 1 4 Control Drawing CSA US Canada ...
Страница 158: ...Appendix D Manufacturer s EC Declarations 158 Senscient ELDS Rev 15 GB 13 Appendix D Manufacturer s EC Declarations ...
Страница 159: ...Appendix D Manufacturer s EC Declarations Senscient ELDS Rev 15 159 GB ...
Страница 160: ...Appendix D Manufacturer s EC Declarations 160 Senscient ELDS Rev 15 GB ...
Страница 184: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose ...