Installation Design & Engineering
36
Senscient ELDS™
Rev 15
GB
3.2.5 Supporting Structure
The Transmitter and Receiver units should be fixed to rigid, stable supporting structures using the
mounting brackets supplied.
The maximum movement of the supporting structure under all anticipated operating
conditions must be ±0.5º.
If no suitable mounting structure already exists then structures similar to that shown below are
recommended:
The pipe can be filled with concrete to provide extra stability if necessary.
100mm to 150mm (4” to 6”) dia. steel pipe,
nominal 6mm wall thickness
up to
3m
500mm
minimum
500mm
minimum
Concrete foundation
500mm
minimum
Содержание Senscient ELDS 1000 series
Страница 1: ...Operating Manual Senscient ELDS 1000 2000 Series Open Path Cross Duct Gas Detectors A 5170 0 Rev 15 ...
Страница 58: ...Installation Commissioning 58 Senscient ELDS Rev 15 GB 2 x Mounting Brackets ...
Страница 140: ...Certification 140 Senscient ELDS Rev 15 GB 9 1 2 Control Drawing CENELEC ATEX ...
Страница 142: ...Certification 142 Senscient ELDS Rev 15 GB 9 1 4 Control Drawing CSA US Canada ...
Страница 158: ...Appendix D Manufacturer s EC Declarations 158 Senscient ELDS Rev 15 GB 13 Appendix D Manufacturer s EC Declarations ...
Страница 159: ...Appendix D Manufacturer s EC Declarations Senscient ELDS Rev 15 159 GB ...
Страница 160: ...Appendix D Manufacturer s EC Declarations 160 Senscient ELDS Rev 15 GB ...
Страница 184: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose ...