![MSA Senscient ELDS 1000 series Скачать руководство пользователя страница 35](http://html.mh-extra.com/html/msa/senscient-elds-1000-series/senscient-elds-1000-series_operating-manual_1846249035.webp)
Installation Design & Engineering
Senscient ELDS™
Rev 15
35
GB
In order to fit the alignment telescope used during the alignment process, a clear
accessible arc of at least 30cm radius is required close to the unit as shown above.
CAUTION
For reliable operation, a clear beam-path of at least 10cm radius or greater is recommended.
When selecting locations for ELDS units, ensure that only one ELDS Transmitter unit is within
the field-of-view and pointing towards any ELDS Receiver unit. Do NOT run ELDS beam-paths
such that there are multiple Transmitters running along the same axis, because the Receiver at
the end of the run will see laser signals from all of the Transmitters on this axis and this may
cause problems. Detailed guidance is provided in section 3.2.10.
Telescope clearance arc
radius - more than 30cm
Beam clearance arc -
radius more than 10cm
Содержание Senscient ELDS 1000 series
Страница 1: ...Operating Manual Senscient ELDS 1000 2000 Series Open Path Cross Duct Gas Detectors A 5170 0 Rev 15 ...
Страница 58: ...Installation Commissioning 58 Senscient ELDS Rev 15 GB 2 x Mounting Brackets ...
Страница 140: ...Certification 140 Senscient ELDS Rev 15 GB 9 1 2 Control Drawing CENELEC ATEX ...
Страница 142: ...Certification 142 Senscient ELDS Rev 15 GB 9 1 4 Control Drawing CSA US Canada ...
Страница 158: ...Appendix D Manufacturer s EC Declarations 158 Senscient ELDS Rev 15 GB 13 Appendix D Manufacturer s EC Declarations ...
Страница 159: ...Appendix D Manufacturer s EC Declarations Senscient ELDS Rev 15 159 GB ...
Страница 160: ...Appendix D Manufacturer s EC Declarations 160 Senscient ELDS Rev 15 GB ...
Страница 184: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose ...