ASDU sequence optimization
With this parameter, you can set which method is to be used for optimizing
the ASDU types. The standard enables optimization in order to be able to
transfer multiple value changes in a telegram in a sequence of ascending in-
formation object addresses. This is displayed by the sequence bit. The se-
lection of ASDU types for which this optimization is allowed is based on the
edition of the standard.
You can select the following options:
Option
Description
None
The device does not optimize the ASDU types.
Ed. 1
Optimization in accordance with IEC 60870 Edition 1
(Type 1, 3, 9, 11, 21, 126).
Ed. 1 Amendment2
Optimization in accordance with IEC 60870 Edition 1,
Amendment 2 (Type 1, 3, 9, 11, 13, 15 21, 126).
Ed. 2
Optimization in accordance with IEC 60870 Edition 2
(Type 1, 3, 5, 7, 9, 11, 13, 15, 20, 21, 126).
Table 19: ASDU sequence optimization
Receiver IP address
You can use this parameter to set the IP address of the receiver.
9.1.6.4 Configuring Modbus
If you want to use the Modbus control system protocol, you must set the cor-
responding parameters depending on the Modbus type selected. Also refer
to the section Configuring the network if you want to use Modbus TCP.
1. Go to
Settings > Parameters > System > Modbus
.
2. Select the desired parameter.
3. Set the parameter.
4. Press the
Accept
button to save the modified parameter.
Modbus type
You can use this parameter to set the Modbus type. You can select the fol-
lowing options:
▪ RTU
▪ TCP
▪ ASCII
TCP port
You can use this parameter to set the TCP port.