9 Operation
Maschinenfabrik Reinhausen GmbH 2021
108
7817454/02 EN
TAPCON
®
230 Expert
1. Go to
Settings > Parameters > Grid > TAPCON® 2xx retrofit
.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the
Accept
button to save the modified parameter.
TAPCON® 2xx retrofit
You can use this parameter to activate or deactivate the Retrofit TAPCON®
2xx function.
If you activate this parameter, you have to reverse the prefix of the "Phase
angle correction" parameter for the transformer data (from
-
to
+
or from
+
to
-
).