9.3.2.1 R&X compensation
R&X compensation can compensate for voltage losses on the lines and
therefore ensure correct voltage at the load. This requires precise line data.
After you have entered all of the line data, the device automatically calcu-
lates the ohmic and inductive voltage drop and takes this into account for au-
tomatic voltage regulation.
U
Tr
VT
CT
U
Line-Drop
U
Load
U
I
R
X
Figure 53: Equivalent circuit of R&X compensation
Figure 54: Phasor diagram of R&X compensation
To use R&X compensation, you have to enter the following line data:
▪ Ohmic resistance load in mΩ/m
▪ Inductive resistance load in mΩ/m
▪ Length of line in km
1. Go to
Settings > Parameters > On-load tap-changer regulator > Com-
pensation
.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the
Accept
button to save the modified parameter.