9 Operation
Maschinenfabrik Reinhausen GmbH 2021
114
7817454/02 EN
TAPCON
®
230 Expert
TDSC U0
You can use this parameter to set the desired value which is to be used
when the measured active power is 0.
1. Go to
Settings > Parameters > Control > TDSC U0
.
2. Enter desired value at active power 0.
3. Press the
Accept
button to save the modified parameter.
TDSC Pmax/Pmin
You can use these parameters to set the maximum and minimum active
power value at which the maximum and minimum active power-dependent
desired value is to be used for regulation.
1. Go to
Settings > Parameters > Control > TDSC Pmax/Pmin
.
2. Enter active power for maximum/minimum desired value.
3. Press the
Accept
button to save the modified parameter.
Bandwidth
You can use this parameter to set the maximum permissible deviation of the
measured voltage U
actual
from the desired value U
desired
.
In order to set the correct value, the transformer step voltage and nominal
voltage must be known. Note that a large bandwidth will result in a large
control deviation.
The bandwidth must always be greater than the following value:
|
±
B
|
≥ 0,6×
U
n
- 1
-
U
n
U
N
× 100
%
U
n-1
Step voltage of tap position n-1
U
n
Step voltage of tap position n
U
N
Nominal voltage
Содержание TAPCON 230 AVT
Страница 1: ...Voltage regulator TAPCON 230 Expert Operating instructions 7817454 02 EN ...
Страница 165: ......