9 Operation
Maschinenfabrik Reinhausen GmbH 2021
101
7817454/02 EN
TAPCON
®
230 Expert
If the measured value is higher than the upper limit (> or >>) or lower than
the lower limit (< or <<), the device transmits an event message.
U>>
U<
U
t
U>
U<<
t
V
t
E
H
Figure 45: Example of voltage monitoring with the limit value Overvoltage U> being exceeded
U>> Overvoltage U>>
U> Overvoltage U>
U< Undervoltage U<
U<< Undervoltage U<<
t
V
Delay time
t
E
Event duration
H Hysteresis
1. Go to
Settings > Parameters > Grid > Voltage monitoring
.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the
Accept
button to save the modified parameter.
You can set additional parameters for each limit value:
Mode
You can use this parameter to set which limit value you would like to use:
▪ Absolute: The device uses the absolute limit value in V.
▪ Relative: The device uses the relative limit value in %, relative to the de-
sired voltage value.