9 Operation
Maschinenfabrik Reinhausen GmbH 2021
104
7817454/02 EN
TAPCON
®
230 Expert
Reaction
You can use this parameter to set the behavior of the device if the measured
value is higher than the upper limit (> or >>) or lower than the lower limit (<
or <<). You can select the following options:
Setting
Behavior
Off
No reaction.
Auto blocking
Automatic regulation is blocked.
You can continue to perform tap-change operations in
manual mode.
Auto/manual blocking
Automatic regulation is blocked.
You
cannot
perform tap-change operations in manual
mode.
Table 37: Behavior when an event message is issued
9.2.4 Power monitoring
For monitoring the transformer's current power, you can set the following
limit values:
Measured value
Lower
limit 2
Lower
limit 1
Upper
limit 1
Upper
limit 2
Apparent power
S<<
S<
S>
S>>
Active power
P<<
P<
P>
P>>
Reactive power
Q<<
Q<
Q>
Q>>
Power factor (amount)
|cos φ|<<
|cos φ|<
-
-
Table 38: Limit values for power monitoring
1. Go to
Settings > Parameters > Grid > Power monitoring
.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the
Accept
button to save the modified parameter.
You can set additional parameters for each limit value:
Absolute
You can use this parameter to specify a limit value.
Hysteresis
You can use this parameter to set the hysteresis. You can use this to avoid
the unnecessary generation of messages if the measured value fluctuates
around a threshold value.