9 Operation
Maschinenfabrik Reinhausen GmbH 2021
75
7817454/02 EN
TAPCON
®
230 Expert
9.1.6.2 Configuring IEC 60870-5-101
If you want to use the IEC 60870-5-101 control system protocol, you must
set the following parameters.
1. Go to
Settings > Parameters > System > IEC 60870-5-101
.
2. Select the desired parameter.
3. Set the parameter.
4. Press the
Accept
button to save the modified parameter.
Serial interface
You can use this parameter to select the serial interface for data transmis-
sion. You can select the following options:
▪ RS232
▪ RS485
Baud rate
You can use this parameter to set the serial interface's baud rate. You can
select the following options:
▪ 9600 baud
▪ 19200 baud
▪ 38400 baud
▪ 57600 baud
▪ 115200 baud
Number of link address octets
You can use this parameter to set how many octets are provided for the link
address.
Link address
You can use this parameter to set the link address.
Number of ASDU address octets
You can use this parameter to set how many octets are provided for the
ASDU address.
ASDU address
You can use this parameter to set the address of the ASDU.
No. of information object address octets
You can use this parameter to set how many octets are provided for the in-
formation object address.