6 Mounting
Maschinenfabrik Reinhausen GmbH 2021
51
7817454/02 EN
TAPCON
®
230 Expert
Serial fiber-optic cable
You will need the CM-0847 FO converter if you want to connect your control
system via the serial fiber-optic cable.
► Connect the serial fiber-optic cable and the converter to the CPU-X5 inter-
face.
6.4.5.4 Ethernet interface
► Connect the Ethernet cable (RJ45 connector) to the COM-X3 interface.
6.4.6 Wiring voltage measurement/current measurement UI
You must fuse the voltage measurement circuit in accordance with the con-
ductor cross section used. You can use the following fuse types:
Miniature circuit breaker
Safety fuse
Standard
IEC 60947-2
IEC 60269
Rated voltage
400 V (L-L) or 230 V (L-N)
Rated current
30 mA...16 A
Characteristics
B, C, K or Z
Fast-acting, medium-act-
ing or delayed-acting
Rated switching capacity
50 kA
For installation in accordance with IEC 61010-2-30
CAT II: 10 kA
Table 11: Permissible fuse types
1. Voltage measurement: Feed the wires into the terminals UI:X7-4 (N con-
ductor) and UI:X7-3 (L conductor) and fasten them using a screwdriver.
Figure 36: UI:X7-4/3