9 Operation
Maschinenfabrik Reinhausen GmbH 2021
74
7817454/02 EN
TAPCON
®
230 Expert
Severity level
You can set which syslog messages the device will send. You can also acti-
vate or deactivate messages for each severity level.
Severity level
Description
Emergency
The system is unusable.
Alert
Immediate intervention required.
Critical
Critical state
Error
Error state
Warning
Warning state
Notice
Notice state
Info
Information state
Debug
Debug state
Table 17: Severity levels
9.1.6 SCADA
The following section describes how you can configure the device for con-
nection to a control system (SCADA). You can download the data points with
the help of the export manager.
9.1.6.1 Configuring IEC 61850
If you want to use the IEC 61850 control system protocol, you must set the
following parameters. Also refer to the section Configuring the network.
1. Go to
Settings > Parameters > System > IEC 61850
.
2. Select the desired parameter.
3. Set the parameter.
4. Press the
Accept
button to save the modified parameter.
IED name
You can use this parameter to assign the device an IED name in order for it
to be identified in the IEC 61850 network.
9.1.6.1.1 Downloading an ICD file
You can download the ICD file from the device via the Import/Export Man-
ager. To do this, you have to establish an Ethernet connection between the
device and your PC.