5 Mounting
Maschinenfabrik Reinhausen GmbH 2015
59
4427410/00 EN
OILTAP® R
3.
Put part B of plug connector back in bracket.
Figure 45: Placing part B of plug connector in bracket
4.
Swivel part A of plug connector out of on-load tap-changer head in di-
rection indicated by arrow until it is between the pipe connections and
the cable cannot be damaged when pulling out the diverter switch insert.
Figure 46: Swiveling out part A of plug connector
Lifting out diverter switch insert
1.
Loosen bolts and safety elements on carrier plate of diverter switch in-
sert.
NOTICE!
Make sure that parts do not fall into the oil compartment.
Parts in the oil compartment may block the diverter switch insert, there-
by damaging the on-load tap-changer and transformer. Check that you
have the same number of parts when disassembling and reassembling.
Figure 47: Carrier plate of diverter switch insert