10 Technical data
Maschinenfabrik Reinhausen GmbH 2015
186
4427410/00 EN
OILTAP® R
Technical data
An overview of all key technical data for the on-load tap-changer and motor-
drive unit exists in the form of separate documents, which are available on
request.
Technical data for protective relay
General technical data
Housing
Outdoor model
Degree of protection
Relay actuation
Flap valve with aperture
Weight
About 3.5 kg
Oil flow speed of available types
when tripping (oil temperature 20
°C)
0.65 m/s
1.20 m/s
3.00 m/s
4.80 m/s
Table 11: General technical data
Tripping circuit
The protective relay can be supplied with either a normally open (NO) or a
normally closed (NC) dry-reed magnetic switch (see dimensional drawing
supplied).
Other contact combinations are available as special version.
Electrical data for normally open (NO) or normally closed (NC) dry-reed
magnetic switch
AC switching capacity
DC switching capacity
1.2 VA…400 VA
1.2 W…250 W
Maximum admissible voltage
AC/DC
Minimum admissible voltage
AC/DC
250 V
24 V
Maximum switched current AC/DC
Minimum switched current AC/DC
2 A
4.8 mA at 250 V
10
10.1
Содержание OILTAP R
Страница 1: ...On Load Tap Changer OILTAP R Installation and Commissioning Instructions 4427410 00 EN ...
Страница 123: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2015 123 4427410 00 EN OILTAP R 3 Open terminal box Figure 154 Terminal box ...
Страница 149: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2015 149 4427410 00 EN OILTAP R Figure 188 Drive shaft with cardan joint ...
Страница 204: ......
Страница 205: ......