9 Fault elimination
Maschinenfabrik Reinhausen GmbH 2015
181
4427410/00 EN
OILTAP® R
Error pattern
Action
Tripping of protective relay (for example RS)
Also contact MR.
Tripping of pressure relief device (for example
MPreC®)
Remove diverter switch insert following mainte-
nance manual for the relevant on-load tap-changer.
Depending on the cause of tripping, take measure-
ments/carry out checks on the transformer.
Contact MR.
Activation of pressure monitoring device (for exam-
ple DW 2000)
Also contact MR.
Activation of tap-change supervisory control
The motor-drive unit can no longer be electrically
actuated once the tap-change supervisory control
has been activated. Manual operation of the motor-
drive unit via the hand crank when the transformer
is switched on is prohibited.
Remove diverter switch insert following mainte-
nance manual for the relevant on-load tap-changer.
Depending on the cause of tripping, take measure-
ments/carry out checks on the transformer.
Also contact MR.
Activation of rupture disk in on-load tap-changer
head cover
Remove diverter switch insert following mainte-
nance manual for the relevant on-load tap-changer.
Depending on the cause of tripping, take measure-
ments/carry out checks on the transformer.
Also contact MR.
Tripping of motor protective switch in motor-drive
unit
Request "Information sheet on motor protective
switch tripping" from MR, complete and return to
MR.
Tripping of signaling contact that indicates that the
oil has fallen below the minimum oil level in the on-
load tap-changer oil conservator
Check pipework system (pipes etc.) and on-load
tap-changer head for leaks. Check oil level and oil
quality of diverter switch oil in accordance with op-
erating instructions for on-load tap-changer. If the
oil falls below the limit values, also contact MR.
On-load tap-changer not changing tap position
(sluggishness, Raise keys/Lower keys not working,
diverter switch action not audible)
Contact MR.
No change in voltage on transformer despite
change in position on motor-drive unit
Contact MR.
Tap position indicator on motor-drive unit and on-
load tap-changer different
Contact MR.
Noises on drive shaft or motor-drive unit when
changing tap position
Ensure proper mounting of the drive shaft in ac-
cordance with its operating instructions. Check that
hose clips and protective covers are seated cor-
rectly. Contact MR in the event of noise from the
motor-drive unit.