5 Mounting
Maschinenfabrik Reinhausen GmbH 2015
108
4427410/00 EN
OILTAP® R
3.
Lift out the diverter switch insert slowly and vertically.
Figure 128: Lifting out diverter switch insert
4.
CAUTION!
Place the diverter switch insert on a level surface and se-
cure it against tipping. An unstably positioned diverter switch insert may
tip, resulting in injuries and damage.
Opening kerosene drain plug
►
NOTICE!
Unscrew kerosene drain plug with extended socket wrench
counter-clockwise until it starts to get hard to turn.Never unscrew the
kerosene drain plug all the way.
Figure 129: Kerosene drain plug
Inserting diverter switch insert
Proceed as follows to insert the diverter switch insert.
5.3.8.2.2
5.3.8.2.3