9 Fault elimination
Maschinenfabrik Reinhausen GmbH 2015
182
4427410/00 EN
OILTAP® R
Error pattern
Action
Red message on monitoring unit
If possible read out database and send to MR
along with error code.
Warning or tripping of Buchholz relay on transform-
er
Notify manufacturer of transformer.
Deviation from desired value when measuring
winding resistance of transformer
Contact manufacturer of transformer and, if neces-
sary, MR and provide measured values.
Deviation from desired value during dissolved gas
analysis (transformer oil)
Contact manufacturer of transformer and, if neces-
sary, MR and provide measured values.
Deviation from desired value during transformer ra-
tio test
Contact manufacturer of transformer and, if neces-
sary, MR and provide measured values.
Deviation from limit value for diverter switch oil val-
ues
Carry out oil change, check oil conservator breath-
er of on-load tap-changer.
Table 10: Fault elimination
Tripping of the protective relay and re-commissioning the
transformer
WARNING
Danger of death or severe injury!
Danger of death or severe injury if on-load tap-changer and transformer are
insufficiently tested!
► Be sure to check on-load tap-changer and transformer after the protec-
tive relay has been tripped. The diverter switch insert or selector switch
insert must be removed in order to do this.
► Only use the equipment again when you are sure there is no damage to
the on-load tap-changer or transformer.
When the circuit breakers have been tripped by the protective relay, proceed
as follows:
1.
Establish time of tripping.
2.
Determine operating position of on-load tap-changer.
3.
As a precaution, block the motor-drive unit by tripping the motor protec-
tive switch to prevent the on-load tap-changer being actuated by remote
control.
4.
Check on-load tap-changer head cover. If oil is leaking, shut the oil con-
servator stop valve immediately.
5.
Check whether the flap valve of the protective relay is in the OFF or IN
SERVICE position.
9.1
Содержание OILTAP R
Страница 1: ...On Load Tap Changer OILTAP R Installation and Commissioning Instructions 4427410 00 EN ...
Страница 123: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2015 123 4427410 00 EN OILTAP R 3 Open terminal box Figure 154 Terminal box ...
Страница 149: ...5 Mounting Maschinenfabrik Reinhausen GmbH 2015 149 4427410 00 EN OILTAP R Figure 188 Drive shaft with cardan joint ...
Страница 204: ......
Страница 205: ......