7 Transporting transformer to the operating site
Maschinenfabrik Reinhausen GmbH 2015
170
4427410/00 EN
OILTAP® R
5.
Open air-vent valve again and drain off around 5–10 liters of oil via the
pipe connection S until the area under the on-load tap-changer head
cover is free of oil.
6.
Loosen 24 screws M10/wrench size 17 with safety elements on on-load
tap-changer head cover.
7.
Remove the on-load tap-changer head cover.
8.
Extract oil via pipe connection S.
9.
Open stop-cock between oil conservator and oil compartment.
ð
The oil from the oil conservator flows into the oil compartment.
10. Extract oil via pipe connection S.
11. Place the on-load tap-changer head cover on the on-load tap-changer
head.
12. Use 24 screws M10/wrench 17 and safety elements to screw down on-
load tap-changer head cover (tightening torque 34 Nm).