PAGE 18 — DCA220SSJU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #3 (02/10/17)
GENERAL PARALLELING INFORMATION (OPTION)
THREE PHASE 480V/208V PARALLEL WIRING VIA
CAMLOCKS
REQUIRED EQUIPMENT
4/0 Single Conductor Cable (User Supplied)
CAT5E Shielded Cable or Better (User Supplied)
Power Distribution Panel (User Supplied)
The following procedure intended to assist the user with
the parallel wiring configuration for the DCA220SSJU4F
generator using the camlok connector panel.
PREPARATION
1. Make sure generator is turned off and engine is cool.
2. Disconnect any loads connected to the generator.
3. Place the main circuit breaker in the
OFF position.
4. Place the generator in an area free of dirt and debris
Make sure it is on secure level ground.
5. Disconnect
negative
battery cable from the battery.
3Ø-480 VAC PARALLEL WIRING CONFIGURATION
1. Using 4/0 cables connect the two generators to the
power distribution panel as referenced in the 3Ø-480V
parallel wiring diagram.
NOTICE
Only a
qualified service technician or licensed
electrician with proper training should perform
this installation. Follow all shop safety rules when
performing this installation.
DANGER
To prevent arcing make sure cables are securely tighten
at power distribution panel, the possibility exist of the
unit catching on fire thus causing equipment damage
and severe bodily harm.
NOTICE
When connecting load cables to the power distribution
panel be sure to select the correct size of the load
cables to handle full load/amperage of both generators
(parallel).
3Ø-208 VAC PARALLEL WIRING CONFIGURATION
1. Using 4/0 cables connect the two generators to the
power distribution panel as referenced in the 3Ø-208V
parallel wiring diagram.
ETHERNET CABLE CONNECTION
1. Connect a CAT5E Ethernet cable (shielded) between
port 1 on both generators as shown in Figure 3.
Figure 3. Ethernet Cable Connection
2. Reference Table 4 for additional Ethernet port
connections.
3. Reconnect battery.
4. Start generator as outlined in start up section of this
manual.
CAT5E ETHERNET
CABLE (SHIELDED)
CAT5E PORT 1
GENERATOR 1
CAT5E PORT 1
GENERATOR 2
PORT 2
PORT 2
Table 4. Ethernet Cable Connections
Generator 1
Generator 2
Port 2
Port 1
Port 1
Port 2
Port 2
Port 2
Содержание DCA220SSJU4F
Страница 4: ...PAGE 4 DCA220SSJU4F 60 HZ GENERATOR OPERATION MANUAL REV 3 02 10 17 NOTES ...
Страница 51: ...DCA220SSJU4F 60 HZ GENERATOR OPERATION MANUAL REV 3 02 10 17 PAGE 51 GENERATOR WIRING DIAGRAM BASLER OPTION ...
Страница 52: ...PAGE 52 DCA220SSJU4F 60 HZ GENERATOR OPERATION MANUAL REV 3 02 10 17 ENGINE WIRING DIAGRAM ECU 835 ...
Страница 54: ...PAGE 54 DCA220SSJU4F 60 HZ GENERATOR OPERATION MANUAL REV 3 02 10 17 NOTES ...
Страница 57: ...DCA220SSJU4F 60 HZ GENERATOR OPERATION MANUAL REV 3 02 10 17 PAGE 57 BATTERY CHARGER WIRING DIAGRAM OPTION ...
Страница 79: ...DCA220SSJU4F 60 HZ GENERATOR OPERATION MANUAL REV 3 02 10 17 PAGE 79 NOTES ...