DCA220SSJU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #3 (02/10/17) — PAGE 45
RADIATOR CLEANING
The radiator (Figure 59) should be sprayed (cleaned) with
a high pressure washer when excessive amounts of dirt
and debris have accumulated on the cooling fins or tube.
When using a high pressure washer, stand at least 5 feet
(1.5 meters) away from the radiator to prevent damage to
the fins and tube.
Figure 59. Radiator Cleaning
GENERATOR STORAGE
For long term storage of the generator the following is
recommended:
Drain the fuel tank completely. Treat with a fuel stabilizer
if necessary.
Completely drain the oil from the crankcase and refill if
necessary with fresh oil.
Clean the entire generator, internal and external.
Cover the generating set and store in a clean, dry place.
Disconnect the battery.
Make sure engine coolant is at proper level.
If generator is mounted on a trailer, jack trailer up and
place on blocks so tires do not touch the ground or block
and completely remove the tires.
WARNING
Allow engine to
cool when flushing out
radiator. Flushing the radiator while hot
could cause serious burns from water or
steam.
JACKET WATER HEATER AND INTERNAL BATTERY
CHARGER 120 VAC INPUT RECEPTACLES
(OPTIONAL)
This generator can be optionally equipped with two 120
VAC, 20 amp input receptacles located on the output
terminal panel.
The purpose of these receptacles is to provide power via
commercial power to the
jacket water heater and internal
battery charger.
These receptacles will
ONLY function when commercial
power has been supplied to them (Figure 60). To apply
commercial power to these receptacles, a power cord of
adequate size will be required (See Table 7).
When using the generator in
hot climates there is no
reason to apply power to jacket water heater. However, if the
generator will be used in
cold climates it is always a good
idea to apply power to the jacket water heater at all times.
To apply power to the jacket water heater simply apply
power to the jacket water heater receptacle via commercial
power using an power cord of adequate size.
Figure 60. Battery Charger and Jacket Water
Heater Power Connections
If the generator will be used daily, the battery should
normally not require charging. If the generator will be idle
(not used) for long periods of time, apply power to the
battery charger receptacle via commercial power using a
power cord of adequate size.
NOTICE
To ensure adequate starting capability, always have
power applied to the generator's internal battery
charger..
MAINTENANCE
Содержание DCA220SSJU4F
Страница 4: ...PAGE 4 DCA220SSJU4F 60 HZ GENERATOR OPERATION MANUAL REV 3 02 10 17 NOTES ...
Страница 51: ...DCA220SSJU4F 60 HZ GENERATOR OPERATION MANUAL REV 3 02 10 17 PAGE 51 GENERATOR WIRING DIAGRAM BASLER OPTION ...
Страница 52: ...PAGE 52 DCA220SSJU4F 60 HZ GENERATOR OPERATION MANUAL REV 3 02 10 17 ENGINE WIRING DIAGRAM ECU 835 ...
Страница 54: ...PAGE 54 DCA220SSJU4F 60 HZ GENERATOR OPERATION MANUAL REV 3 02 10 17 NOTES ...
Страница 57: ...DCA220SSJU4F 60 HZ GENERATOR OPERATION MANUAL REV 3 02 10 17 PAGE 57 BATTERY CHARGER WIRING DIAGRAM OPTION ...
Страница 79: ...DCA220SSJU4F 60 HZ GENERATOR OPERATION MANUAL REV 3 02 10 17 PAGE 79 NOTES ...