DCA220SSJU4F 60 HZ GENERATOR• OPERATION MANUAL — REV. #3 (02/10/17) — PAGE 17
SEQUENCING
These generators are capable of sequencing for control
of balanced maintenance schedules. As described
above, these generators can start and stop as demand
raises or lowers. In addition, if the units get to the point of
maintenance, it will ramp off and start the next generator to
relieve it based on the time remaining on the maintenance
timer.
After maintenance is performed, the maintenance timers
should be reset to the recommended service interval. This
is usually 250 hours depending on the engine oil type.
MAINTENANCE INTERVAL
Maintenance intervals are factory set for 250 hours.
The maintenance interval timer will count down to zero
indicating that it is time for the unit to be serviced.
Once the timer counts down to zero, a pre-alarm will appear
indicating that the unit is due for maintenance. To reset the
maintenance interval back to the default time of 250 hours,
press and hold the “Reset” button for ten seconds.
To reset the maintenance interval using the reset button,
the Maintenance Due pre-Alarm must be active, and the
Basler controller must display the “Overview Screen” (Main
Screen).
If the maintenance timer has not yet expired and it is
desired to reset the unit back to 250 hours, navigate back
to the settings menu. Settings Menu->System Parameters-
>Engine Statistics->Hours To Maintenance.
When highlighted, press the “Edit” button. Username and
Password is required. User Name is
A and Password is
A. Use the up arrow button (
) and scroll to the alpha
character
A, then press edit to select.
Next, the cursor will move to the
password
field, press the
up arrow button (
) and scroll to the alpha character
A,
then press edit to select.
NOTICE
Ethernet communication is required when the
generators are configured for the sequencing mode
of operation.
GENERAL PARALLELING INFORMATION (OPTION)
Full Password key sequence is ^ Edit ^Edit. The set-point for
the desired hours until maintenance can now be changed.
Press edit to save.
Pre-alarm Silence allows the user to suppress the toggling
of the alarm screen when a new Pre-alarm becomes active.
While a Pre-alarm is active, pressing the Alarm Silence
button will suppress the fault display.
This happens to be very handy function when the
“Maintenance Interval” Pre-Alarm occurs. Right after the
Pre-Alarm occurs it will begin toggling between the
pre-
alarm
and the
overview screen
.
While in this mode, pressing the reset button does not reset
the maintenance interval. In order to reset the maintenance
interval the overview screen
must
be selected.
Pressing the alarm silence button will stop the toggling
between the pre-alarm and the overview screen.
Once the overview screen is selected, the maintenance
interval can be reset by pressing and holding the reset
button for 10 seconds.
ANALOG LOAD SHARING
If no Ethernet cable is available or if paralleling to other
equipment with traditional analog load sharing, there is a
terminal block to connect a shielded wire pair between the
two controls. The voltage ranges are programmable with
the default value set by Multiquip at 0-3VDC, which is a
common voltage for most controllers.
Please note that when in the load sharing mode the voltage
is set to droop at 5%. This setting is programmable, but the
default setting is 5%.
Содержание DCA220SSJU4F
Страница 4: ...PAGE 4 DCA220SSJU4F 60 HZ GENERATOR OPERATION MANUAL REV 3 02 10 17 NOTES ...
Страница 51: ...DCA220SSJU4F 60 HZ GENERATOR OPERATION MANUAL REV 3 02 10 17 PAGE 51 GENERATOR WIRING DIAGRAM BASLER OPTION ...
Страница 52: ...PAGE 52 DCA220SSJU4F 60 HZ GENERATOR OPERATION MANUAL REV 3 02 10 17 ENGINE WIRING DIAGRAM ECU 835 ...
Страница 54: ...PAGE 54 DCA220SSJU4F 60 HZ GENERATOR OPERATION MANUAL REV 3 02 10 17 NOTES ...
Страница 57: ...DCA220SSJU4F 60 HZ GENERATOR OPERATION MANUAL REV 3 02 10 17 PAGE 57 BATTERY CHARGER WIRING DIAGRAM OPTION ...
Страница 79: ...DCA220SSJU4F 60 HZ GENERATOR OPERATION MANUAL REV 3 02 10 17 PAGE 79 NOTES ...