6.14.3.1
Connecting the main supply
The control cabinet must be supplied with power via a feeder cable.
It must be possible to switch off the supply using a main switch
The cross sections of the supply lines must be adapted to match the connected
load of the control cabinet type and cable lengths and must be protected by a
suitable circuit breaker. The electrical data is included in your project-specific
documents.
As the inverter has an increased ground leakage current, the minimum cross-
section of the PE conductor must be observed.
6.15
Emergency power supply
For safety reasons, an emergency power supply must be provided for the control
cabinets, so that all tracker arrays can still be moved to the safety position in the
event of a power failure.
A permanent power supply must be ensured for the head station.
The emergency power supply should be designed and tested in accordance with
the respective project.
A control signal must be transferred to the controls during emergency-power
operation.