background image

56

B A T T E R Y   I N F O R M A T I O N

57

M O R N I N G S T A R   C O R P O R A T I O N

9.0

is important to never exceed the manufacturer’s maximum charging voltages. 
Typically, a gel battery is recharged in cycling applications from 14.1V to 
14.4V. The gel design is very sensitive to overcharging.

For both AGM and Gel batteries, the goal is for 100% recombination of gases 
so that no water is lost from the battery. True equalizations are never done, 
but a small boost charge may be needed to balance the individual  
cell voltages.

Other Sealed Batteries:

Automotive and “maintenance-free” batteries are also sealed. However, these 
are not discussed here because they have very poor lifetimes in solar cycling 
applications.

 NOTE: Consult the battery manufacturer for the recommended solar 

charging settings for the battery being used.

  

REMARQUE : Consultez le fabricant de la batterie quant aux réglages 

recommandés de charge solaire pour la batterie utilisée.

9.2  Flooded Batteries

Flooded (vented) batteries are preferred for larger cycling solar systems.  
The advantages of flooded batteries include:
• ability to add water to the cells
• deep cycle capability
• vigorous recharging and equalization

• long operating life

In cycling applications, flooded batteries benefit from vigorous charging and 
equalization cycles with significant gasing. Without this gasing, the heavier 
electrolyte will sink to the bottom of the cell and lead to stratification. This is 
especially true with tall cells. Hydrocaps can be used to limit the gasing water 
loss.

Note that a 4% mixture of hydrogen in air is explosive if ignited. Make certain 
the battery area is well ventilated.

Typical equalization voltages for flooded batteries are from 15.3 volts to 16 
volts. However, a solar system is limited to what the solar array can provide.  
If the equalization voltage is too high, the array I-V curve may go over the 
“knee” and sharply reduce the charging current.

Lead-Calcium: 

Calcium batteries charge at lower voltages (14.2 to 14.4 typically) and have 
strong advantages in constant voltage or float applications. Water loss can be 
only 1/10th of antimony cells. However, calcium plates are not as suitable for 
cycling applications.

Lead-Selenium: 

These batteries are similar to calcium with low internal losses and very low 
water consumption throughout their life. Selenium plates also have poor 
cycling life.

Lead-Antimony:

Antimony cells are rugged and provide long service life with deep discharge 
capability. However, these batteries self-discharge much faster and the self-
discharging increases up to five times the initial rate as the battery ages. 
Charging the antimony battery is typically from 14.4V to 15.0V, with a 120% 
equalization overcharge. While the water loss is low when the battery is new, 
it will increase by five times over the life of the battery.

There are also combinations of plate chemistries that offer beneficial tradeoffs. 
For example, low antimony and selenium plates can offer fairly good cycling 
performance, long life, and reduced watering needs.

 NOTE: Consult the battery manufacturer for the recommended solar 

charging settings for the battery being used.

  

REMARQUE : Consultez le fabricant de la batterie quant aux réglages 

recommandés de charge solaire pour la batterie utilisée.

9.3  L-16 Cells

One particular type of flooded battery, the L-16 group, is often used in larger 
solar systems. The L-16 offers good deep-cycle performance, long life, and 
low cost. 

The L-16 battery has some special charging requirements in a solar system.  
A study found that nearly half of the L-16 battery capacity can be lost if the 
regulation voltage is too low and the time between finish-charges is too long. 
One standard charging program in the TriStar is specifically for L-16 batteries, 
and it provides for higher charging voltages and more frequent equalizations. 
Additional equalizations can also be done manually with the push-button.

A good reference for charging L-16 batteries is a Sandia National Labs report 
(year 2000) titled “PV Hybrid Battery Tests on L-16 Batteries.” Website: www.
sandia.gov/pv.

  

NOTE: The best charging algorithm for flooded, deep-cycle batteries 

depends on the normal depth-of-discharge, how often the battery is 

cycled, and the plate chemistry. Consult the battery manufacturer for the 

recommended solar charging settings for the battery being used.

  

REMARQUE : Le meilleur algorithme de charge pour les batteries à 

électrolyte liquide à décharge poussée dépend de l’amplitude de la 

décharge, de la fréquence du cycle de batterie et de la composition 

chimique des plaques. Consultez le fabricant de la batterie quant aux 

réglages recommandés de charge solaire pour la batterie utilisée.

Содержание TriStar TS-45

Страница 1: ...peration and Maintenance Manual MAXIMUM POWER POINT TRACKING Solar Battery Charging Load Control Diversion Control For the most recent manual revisions see the version at www morningstarcorp com MODEL...

Страница 2: ...sh Installation 26 3 0 Operation 27 3 1 Operator s Tasks 27 3 2 Push button 27 3 3 LED Indications 28 3 4 Protections and Fault Recovery 29 3 5 Data Logging 32 3 6 Inspection and Maintenance 32 4 0 So...

Страница 3: ...ix 3 LED Indications 70 12 0 Certifications 73 co nt i nued IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important safety installation operating and mantenance instructio...

Страница 4: ...xposure to the elements and do not allow water to enter the controller Install the TriStar PWM in a location that prevents casual contact The TriStar PWM heatsink can become very hot during operation...

Страница 5: ...tain there is enough ventilation to release the gases Never smoke in the battery area If battery acid comes into contact with the skin wash with soap and water If the acid contacts the eye flood with...

Страница 6: ...rez vous que le niveau d lectrolyte de la batterie est correct avant de commencer la charge Ne tentez pas de charger une batterie gel e Recyclez la batterie quand elle est remplac e 1 0 TriStar Descri...

Страница 7: ...he enclosure can be grounded using the ground terminal in the wiring compartment The TriStar is protected from faults electronically with automatic recovery There are no fuses or mechanical parts insi...

Страница 8: ...nto an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help This Class B digital apparatus complies with Canadia...

Страница 9: ...70 amp res pour le TriStar PWM 45 et 90 amp res pour le TriStar PWM 60 M WARNING Installation must comply with all US National Electrical Code and Canadian Electrical Code requirements Breakers and fu...

Страница 10: ...ltage is the same as the nominal battery voltage Do not install a TriStar in a sealed compartment with batteries Never open the TriStar access cover unless both the solar and battery power has been di...

Страница 11: ...cated behind the negative power terminals Each switch is numbered The solar battery charging functions that can be adjusted with the DIP switches follow Control Mode Battery Charging 1 System Voltage...

Страница 12: ...ches Number 2 3 System Voltage Voltage Switch 2 Switch 3 Auto Off Off 12 Off On 24 On Off 48 On On Auto Select 1 2 3 4 5 6 7 8 DIP ON 12 Volts 1 2 3 4 5 6 7 8 DIP ON ON OFF 24 Volts 1 2 3 4 5 6 7 8 DI...

Страница 13: ...some types of telecom equipment or radios the TriStar can be converted to an On Off method of solar charge regulation It should be noted that the On Off solar charge regulation is much less effective...

Страница 14: ...0 56 Nm 5 in lb of torque The maximum length allowed for each battery voltage sense wire is 30 meters 98 ft The battery sense terminal has polarity Be careful to connect the battery positive terminal...

Страница 15: ...er NEC 690 45 A and NEC Table 250 122 minimum sizes for copper grounding wire are TS MPPT 45 10 AWG 5 mm2 TS MPPT 60 M 8 AWG 8 mm2 OR of the same or greater cross sectional area as the PV wires Connec...

Страница 16: ...rform However the operator should be familiar with the basic operation and care of the TriStar as described below 3 1 Operator s Tasks Use the push button as needed see 3 2 below Check the LEDs for st...

Страница 17: ...LVD 0 30V 0 60V 1 20V LVD 0 15V 0 30V 0 60V LVD The load status LEDs are determined by the LVD voltage plus the specified transition voltages As the battery voltage rises or falls each voltage transi...

Страница 18: ...polarity will be damaged Be very careful to connect loads to the controller with correct polarity See Section 5 4 DIP switch fault R Y G sequencing If a DIP switch is changed while there is power to t...

Страница 19: ...d instructions are available on our website 3 6 Inspection and Maintenance WARNING RISK OF ELECTRICAL SHOCK NO POWER OR ACCESSORY TERMINALS ARE ELECTRICALLY ISOLATED FROM DC INPUT AND MAY BE ENERGIZED...

Страница 20: ...troller to the battery is recommended This allows a precise battery voltage input to the controller and more accurate battery charging See Section 4 3 for more information Temperature Compensation All...

Страница 21: ...ing may go into PWM absorption almost every day If the battery temperature is colder the charging will begin to regulate too soon and the battery may not be recharged with a limited solar resource If...

Страница 22: ...ell drift Equalization cycles help to bring all the cells to the same voltage Mix the electrolyte In flooded batteries especially tall cells the heavier acid will fall to the bottom of the cell over t...

Страница 23: ...e to level individual cells This is not an equalization and will not vent gas from sealed batteries that require up to 14 4V charging 12V battery This boost charge for sealed cells allows for adjustab...

Страница 24: ...Battery 12V 24V 48V Switch LVD LVD LVD SOC LVDR LVDR LVDR off off off 11 1 22 2 44 4 8 12 6 25 2 50 4 off off on 11 3 22 6 45 2 12 12 8 25 6 51 2 off on off 11 5 23 0 46 0 18 13 0 26 0 52 0 off on on...

Страница 25: ...ivert excess current to an external load As the battery becomes fully charged the FET switches are closed for longer periods of time to direct more current to the diversion load As the battery charges...

Страница 26: ...on 4 3 Temperature Effects and Battery Voltage Sense 4 4 Equalization 4 5 Float 9 0 Battery Information 6 4 Selecting the Diversion Load It is critical that the diversion load be sized correctly If th...

Страница 27: ...for the same voltage as the system voltage Nominal Voltage TriStar 45 TriStar 60 48V 2700W at 60V 3600W at 60V 24V 1350W at 30V 1800W at 30V 12V 675W at 15V 900W at 15V These maximum power ratings ar...

Страница 28: ...leurs TriStar 6 6 Additional Information Visit Morningstar s website www morningstarcorp com for additional diversion charge control information The website provides expanded technical support for mo...

Страница 29: ...alert the user to an existing fault or alarm In this situation the LED indicators will flash a particular sequence Section 3 3 references these sequences with their associated faults and alarms Flash...

Страница 30: ...al support documents FAQs or to request technical support 9 0 Battery Information The standard battery charging programs in the TriStar controller as described in Section 4 2 are typical charging algo...

Страница 31: ...calcium with low internal losses and very low water consumption throughout their life Selenium plates also have poor cycling life Lead Antimony Antimony cells are rugged and provide long service life...

Страница 32: ...BUTOR AGENT OR EMPLOYEE IS AUTHORIZED TO MAKE ANY MODIFICATION OR EXTENSION TO THIS WARRANTY MORNINGSTAR IS NOT RESPONSIBLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND INCLUDING BUT NOT LIMITE...

Страница 33: ...rol DIP Settings The NOTE The DIP switches should be changed only when there is no power to the controller Turn off disconnect switches and remove power to the controller before changing a DIP switch...

Страница 34: ...ON Figure A1 3 Step 3 DIP Switches 2 3 The auto voltage selection occurs when the battery is connected and the TriStar starts up There should be no loads on the battery that might cause a discharged b...

Страница 35: ...Custom Settings Figure A1 5 Step 3 DIP Switch 4 5 6 Select one of the 7 standard Lighting Control algorithms or select the custom DIP switch for special custom settings using the PC software The defau...

Страница 36: ...ition With switches 1 and 7 in the ON position Diversion Charge Contol is set The OFF settings will operate as follows Switch Function 1 Must be ON to set Diversion Control 2 3 Auto voltage selected 4...

Страница 37: ...rsion Switch 7 On 1 2 3 4 5 6 7 8 DIP ON ON OFF Figure A2 5 Step 3 DIP Switch 7 In the Diversion Charge Control mode DIP switch 7 must be in the ON position DIP Switch Number 8 Battery Equalization Eq...

Страница 38: ...ond Float state G slow blink 1 second on 1 second off Battery State of Charge LED Indications when battery is charging G on 80 to 95 SOC G Y on 60 to 80 SOC Y on 35 to 60 SOC Y R on 0 to 35 SOC R on b...

Страница 39: ...ds for CE marking Immunity EN 61000 4 3 2006 EN 61000 4 6 2009 Emissions CISPR 22 2008 Safety EN60335 1 EN60335 2 29 battery chargers EN 62109 1 2010 TrisStarTM MeterBusTM are trademarks of Morningsta...

Отзывы: