background image

38

B A T T E R Y   C H A R G I N G

39

M O R N I N G S T A R   C O R P O R A T I O N

4.0

These voltage drops will cause some undercharging of the battery. The 
controller will begin PWM absorption, or limit equalization, at a lower battery 
voltage because the controller measures a higher voltage at the controller’s 
terminals than is the actual battery voltage. For example, if the controller is 
programmed to start PWM absorption at 14.4V, when the controller “sees” 
14.4V at its battery terminals, the true battery voltage would only be 14.1V  
if there is a 0.3V drop between the controller and battery.

Two sense wires, sized from 1.0 to 0.25 mm

2

 (16 to 24 AWG), can be used for 

battery voltage sense. Because these wires carry no current, the voltage at 
the TriStar will be identical to the battery voltage. A 2-position terminal is used 
for the connection

Note that the battery sense wires will not power the controller, and the sense 
wires will not compensate for losses in the power wires between the con troller 
and the battery. The battery sense wires are used to improve the accuracy of 
the battery charging.

See Section 2.3 - Step 5 for instructions how to connect the battery sense wires.

4.4 Equalization 

Routine equalization cycles are often vital to the performance and life of a battery 
— particularly in a solar system. During battery discharge, sulfuric acid is 
consumed and soft lead sulfate crystals form on the plates. If the battery remains 
in a partially discharged condition, the soft crystals will turn into hard crystals over 
time. This process, called “lead sulfation,” causes the crystals to become harder 
over time and more difficult to convert back to soft active materials.

Sulfation from chronic undercharging of the battery is the leading cause of 
battery failures in solar systems. In addition to reducing the battery capacity, 
sulfate build-up is the most common cause of buckling plates and cracked 
grids. Deep cycle batteries are particularly susceptible to lead sulfation.

Normal charging of the battery can convert the sulfate back to the soft active 
material if the battery is fully recharged. However, a solar battery is seldom 
completely recharged, so the soft lead sulfate crystals harden over a period of 
time. Only a long controlled overcharge, or equalization, at a higher voltage 
can reverse the hardening sulfate crystals. 

In addition to slowing or preventing lead sulfation, there are also other benefits 
from equalizations of the solar system battery. These include:

Balance the individual cell voltages.

Over time, individual cell voltages can drift apart due to slight differences in 
the cells. For example, in a 12 cell (24V) battery, one cell is less efficient in 
recharging to a final battery voltage of 28.8 volts (2.4 V/c). Over time, that cell 
only reaches 1.85 volts, while the other 11 cells charge to 2.45 volts per cell. 
The overall battery voltage is 28.8V, but the individual cells are higher or lower 
due to cell drift. Equalization cycles help to bring all the cells to the same 
voltage.

Mix the electrolyte.

In flooded batteries, especially tall cells, the heavier acid will fall to the bottom 
of the cell over time. This stratification of the electrolyte causes loss of 
capacity and corrosion of the lower portion of the plates. Gasing of the 
electrolyte from a controlled overcharging (equalization) will stir and remix the 
acid into the battery electrolyte.

  

NOTE: Excessive overcharging and gasing too vigorously can damage 

the battery plates and cause shedding of active material from the plates. 

An equalization that is too high or for too long can be damaging. Review 

the requirements for the particular battery being used in your system.

  

REMARQUE : Une surcharge excessive et un dégagement gazeux trop 

vigoureux peuvent endommager les  plaques de batteries et provoquer 

l’élimination du matériau actif des plaques. Une compensation trop 

élevée ou trop longue peut provoquer des dégâts. Examinez les 

exigences pour la batterie particulière utilisée dans votre système.

4.4.1  Standard Equalization Programs

Both automatic and manual equalizations can be performed using either the 
standard charging programs 

(see 4.2)

 or a custom program 

(see 7.0)

.

Manual Equalization

The TriStar is shipped with the DIP switch set for manual equalization only. 
This is to avoid an unexpected or unwanted automatic equalization. In the 
manual mode, the push-button is used to both start or stop a manual 
equalization. Hold the push-button down for 5 seconds to start or stop an 
equalization (depending on whether an equalization is in progress or not).

The LEDs will confirm the transition (all 3 LEDs blink 2 times). When the 
battery charging enters into equalization, the Green LED will start fast blinking 
2-3 times per second. 

There are no limits to how many times the push-button can be used to start 
and stop equalizations. Equalizations will be terminated automatically per the 
charging program selected if the push-button is not used to manually stop the 
equalization.

Automatic Equalization

If the equalization DIP switch is moved to the ON position 

(see 2.3 - Step 3)

the equalizations will begin automatically per the charging program selected. 
Other than starting, the automatic and manual equalizations are the same and 
follow the standard charging program selected. The push-button can be used 
to start and stop equalizations in both the manual and automatic mode.

4.4.2  Typical Equalizations

The automatic equalizations will occur every 28 days (except L-16 cells at  
14 days). When an equalization begins (auto or manual), the battery charging 
voltage increases up to the equalization voltage (Veq). The battery will remain  
at Veq for the time specified in the selected charging program 

(see table in 4.2)

.

If the time to reach Veq is too long, the maximum equalization cycle time will 
end the equalization. A second manual equalization cycle can be started with 
the push-button if needed.

If the equalization cannot be completed in one day, it will continue the next 
day or days until finished. After an equalization is completed, charging will 
return to PWM absorption.

Содержание TriStar TS-45

Страница 1: ...peration and Maintenance Manual MAXIMUM POWER POINT TRACKING Solar Battery Charging Load Control Diversion Control For the most recent manual revisions see the version at www morningstarcorp com MODEL...

Страница 2: ...sh Installation 26 3 0 Operation 27 3 1 Operator s Tasks 27 3 2 Push button 27 3 3 LED Indications 28 3 4 Protections and Fault Recovery 29 3 5 Data Logging 32 3 6 Inspection and Maintenance 32 4 0 So...

Страница 3: ...ix 3 LED Indications 70 12 0 Certifications 73 co nt i nued IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important safety installation operating and mantenance instructio...

Страница 4: ...xposure to the elements and do not allow water to enter the controller Install the TriStar PWM in a location that prevents casual contact The TriStar PWM heatsink can become very hot during operation...

Страница 5: ...tain there is enough ventilation to release the gases Never smoke in the battery area If battery acid comes into contact with the skin wash with soap and water If the acid contacts the eye flood with...

Страница 6: ...rez vous que le niveau d lectrolyte de la batterie est correct avant de commencer la charge Ne tentez pas de charger une batterie gel e Recyclez la batterie quand elle est remplac e 1 0 TriStar Descri...

Страница 7: ...he enclosure can be grounded using the ground terminal in the wiring compartment The TriStar is protected from faults electronically with automatic recovery There are no fuses or mechanical parts insi...

Страница 8: ...nto an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help This Class B digital apparatus complies with Canadia...

Страница 9: ...70 amp res pour le TriStar PWM 45 et 90 amp res pour le TriStar PWM 60 M WARNING Installation must comply with all US National Electrical Code and Canadian Electrical Code requirements Breakers and fu...

Страница 10: ...ltage is the same as the nominal battery voltage Do not install a TriStar in a sealed compartment with batteries Never open the TriStar access cover unless both the solar and battery power has been di...

Страница 11: ...cated behind the negative power terminals Each switch is numbered The solar battery charging functions that can be adjusted with the DIP switches follow Control Mode Battery Charging 1 System Voltage...

Страница 12: ...ches Number 2 3 System Voltage Voltage Switch 2 Switch 3 Auto Off Off 12 Off On 24 On Off 48 On On Auto Select 1 2 3 4 5 6 7 8 DIP ON 12 Volts 1 2 3 4 5 6 7 8 DIP ON ON OFF 24 Volts 1 2 3 4 5 6 7 8 DI...

Страница 13: ...some types of telecom equipment or radios the TriStar can be converted to an On Off method of solar charge regulation It should be noted that the On Off solar charge regulation is much less effective...

Страница 14: ...0 56 Nm 5 in lb of torque The maximum length allowed for each battery voltage sense wire is 30 meters 98 ft The battery sense terminal has polarity Be careful to connect the battery positive terminal...

Страница 15: ...er NEC 690 45 A and NEC Table 250 122 minimum sizes for copper grounding wire are TS MPPT 45 10 AWG 5 mm2 TS MPPT 60 M 8 AWG 8 mm2 OR of the same or greater cross sectional area as the PV wires Connec...

Страница 16: ...rform However the operator should be familiar with the basic operation and care of the TriStar as described below 3 1 Operator s Tasks Use the push button as needed see 3 2 below Check the LEDs for st...

Страница 17: ...LVD 0 30V 0 60V 1 20V LVD 0 15V 0 30V 0 60V LVD The load status LEDs are determined by the LVD voltage plus the specified transition voltages As the battery voltage rises or falls each voltage transi...

Страница 18: ...polarity will be damaged Be very careful to connect loads to the controller with correct polarity See Section 5 4 DIP switch fault R Y G sequencing If a DIP switch is changed while there is power to t...

Страница 19: ...d instructions are available on our website 3 6 Inspection and Maintenance WARNING RISK OF ELECTRICAL SHOCK NO POWER OR ACCESSORY TERMINALS ARE ELECTRICALLY ISOLATED FROM DC INPUT AND MAY BE ENERGIZED...

Страница 20: ...troller to the battery is recommended This allows a precise battery voltage input to the controller and more accurate battery charging See Section 4 3 for more information Temperature Compensation All...

Страница 21: ...ing may go into PWM absorption almost every day If the battery temperature is colder the charging will begin to regulate too soon and the battery may not be recharged with a limited solar resource If...

Страница 22: ...ell drift Equalization cycles help to bring all the cells to the same voltage Mix the electrolyte In flooded batteries especially tall cells the heavier acid will fall to the bottom of the cell over t...

Страница 23: ...e to level individual cells This is not an equalization and will not vent gas from sealed batteries that require up to 14 4V charging 12V battery This boost charge for sealed cells allows for adjustab...

Страница 24: ...Battery 12V 24V 48V Switch LVD LVD LVD SOC LVDR LVDR LVDR off off off 11 1 22 2 44 4 8 12 6 25 2 50 4 off off on 11 3 22 6 45 2 12 12 8 25 6 51 2 off on off 11 5 23 0 46 0 18 13 0 26 0 52 0 off on on...

Страница 25: ...ivert excess current to an external load As the battery becomes fully charged the FET switches are closed for longer periods of time to direct more current to the diversion load As the battery charges...

Страница 26: ...on 4 3 Temperature Effects and Battery Voltage Sense 4 4 Equalization 4 5 Float 9 0 Battery Information 6 4 Selecting the Diversion Load It is critical that the diversion load be sized correctly If th...

Страница 27: ...for the same voltage as the system voltage Nominal Voltage TriStar 45 TriStar 60 48V 2700W at 60V 3600W at 60V 24V 1350W at 30V 1800W at 30V 12V 675W at 15V 900W at 15V These maximum power ratings ar...

Страница 28: ...leurs TriStar 6 6 Additional Information Visit Morningstar s website www morningstarcorp com for additional diversion charge control information The website provides expanded technical support for mo...

Страница 29: ...alert the user to an existing fault or alarm In this situation the LED indicators will flash a particular sequence Section 3 3 references these sequences with their associated faults and alarms Flash...

Страница 30: ...al support documents FAQs or to request technical support 9 0 Battery Information The standard battery charging programs in the TriStar controller as described in Section 4 2 are typical charging algo...

Страница 31: ...calcium with low internal losses and very low water consumption throughout their life Selenium plates also have poor cycling life Lead Antimony Antimony cells are rugged and provide long service life...

Страница 32: ...BUTOR AGENT OR EMPLOYEE IS AUTHORIZED TO MAKE ANY MODIFICATION OR EXTENSION TO THIS WARRANTY MORNINGSTAR IS NOT RESPONSIBLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND INCLUDING BUT NOT LIMITE...

Страница 33: ...rol DIP Settings The NOTE The DIP switches should be changed only when there is no power to the controller Turn off disconnect switches and remove power to the controller before changing a DIP switch...

Страница 34: ...ON Figure A1 3 Step 3 DIP Switches 2 3 The auto voltage selection occurs when the battery is connected and the TriStar starts up There should be no loads on the battery that might cause a discharged b...

Страница 35: ...Custom Settings Figure A1 5 Step 3 DIP Switch 4 5 6 Select one of the 7 standard Lighting Control algorithms or select the custom DIP switch for special custom settings using the PC software The defau...

Страница 36: ...ition With switches 1 and 7 in the ON position Diversion Charge Contol is set The OFF settings will operate as follows Switch Function 1 Must be ON to set Diversion Control 2 3 Auto voltage selected 4...

Страница 37: ...rsion Switch 7 On 1 2 3 4 5 6 7 8 DIP ON ON OFF Figure A2 5 Step 3 DIP Switch 7 In the Diversion Charge Control mode DIP switch 7 must be in the ON position DIP Switch Number 8 Battery Equalization Eq...

Страница 38: ...ond Float state G slow blink 1 second on 1 second off Battery State of Charge LED Indications when battery is charging G on 80 to 95 SOC G Y on 60 to 80 SOC Y on 35 to 60 SOC Y R on 0 to 35 SOC R on b...

Страница 39: ...ds for CE marking Immunity EN 61000 4 3 2006 EN 61000 4 6 2009 Emissions CISPR 22 2008 Safety EN60335 1 EN60335 2 29 battery chargers EN 62109 1 2010 TrisStarTM MeterBusTM are trademarks of Morningsta...

Отзывы: