background image

42

L O A D   C O N T R O L

43

M O R N I N G S T A R   C O R P O R A T I O N

5.0

5.0  Load and Lighting Control 

5.1  General Load & Lighting Control Notes

IMPORTANT:

5.1.1  Inductive loads

Do not connect inductive loads such as inverters, motors, pumps, 
compressors, generators to the load terminals.  Inductive loads can generate 
large voltage spikes that may damage the controller’s lightning protection 
devices.  Connect inductive loads directly to the battery.

If a heavy load must be connected to the TriStar's load terminals e.g. for LVD 
purposes, contact your dealer or Morningstar Tech Support for a design 
solution.

5.1.2  Parallel TriStars

Two or more TriStars should never be put in parallel for a large load. The 
controllers cannot share the load. 

5.1.3  Reverse Polarity

If the battery is correctly connected (LEDs are on), the load should be 
connected very carefully with regard to polarity (+ / –). 

If the polarity is reversed, the controller cannot detect this. There are no 
indications.

Loads without polarity will not be affected.

Loads with polarity can be damaged. It is possible that the TriStar will go into 
short circuit protection before the load is damaged. If the LEDs indicate a 
“short”, be certain to check for both shorts and reversed polarity connections.

If the controller does not go into short circuit protection, the loads with polarity 
will be damaged.

 CAUTION: Carefully verify the polarity (+ and –) of the load connections 

before applying power to the controller.

  

PRUDENCE : Vérifiez avec précaution la polarité (+ et –) des connexions 

de la charge avant de mettre le contrôleur sous tension.

5.2  Load Control Settings 

The primary purpose of a low voltage load disconnect function (LVD) is to 
protect the system battery from deep discharges that could damage the 
battery. 

In the Load Control mode, the TriStar provides for seven standard LVD 
settings that are selected by the DIP switches. These are described in the 
table below. Custom LVD settings are possible using the PC software (see 
Section 7.0).

 

DIP 

12V 24V 48V  Battery  12V  24V  48V 

 Switch 

LVD 

LVD 

LVD 

SOC% 

LVD

R

 

LVD

R

 

LVD

R

 off-off-off 

11.1 

22.2 

44.4 

12.6 

25.2 

50.4

 off-off-on 

11.3 

22.6 

45.2 

12 

12.8 

25.6 

51.2

 off-on-off 

11.5 

23.0 

46.0 

18 

13.0 

26.0 

52.0

 off-on-on 

11.7 

23.4 

46.8 

23 

13.2 

26.4 

52.8

 on-off-off 

11.9 

23.8 

47.6 

35 

13.4 

26.8 

53.6

 on-off-on 

12.1 

24.2 

48.4 

55 

13.6 

27.2 

54.4

 on-on-off 

12.3 

24.6 

49.2 

75 

13.8 

27.6 

55.2

 on-on-on 

 

Custom 

 

Custom 

 

Custom 

Table 5.1 

The table above describes the standard selectable LVD battery voltages for 
12, 24 and 48 volt systems. The LVD

R

 values are the load reconnect set-

points. The “Battery SOC %” provides a general battery state-of-charge figure 
for each LVD setting. The actual battery SOC can vary considerably 
depending on the battery condition, discharge rates, and other specifics of the 
system.

  

NOTE: The lowest LVD settings are intended for applications such as 

telecom that only disconnect the load as a last resort. These lower LVD 

settings will deeply discharge the battery and should not be used for 

systems that may go into LVD more than once a year.

  

REMARQUE : Les réglages les plus bas du disjoncteur basse tension sont 

prévus pour les applications comme celles de télécom qui ne 

déconnectent la charge qu’en dernier recours. Ces réglages les plus bas 

du disjoncteur basse tension déchargent fortement la batterie et ne 

doivent pas être utilisés avec les systèmes qui risquent de déclencher le 

disjoncteur basse tension plus d’une fois par an.

The LVD values in table 5.1 above are current compensated. Under load, the 
battery voltage will be reduced in proportion to the current draw by the load. A 
short-term large load could cause a premature LVD without the current 
compensation. The LVD values in the table above are adjusted lower per  
the following table:

  

TS-45 

TS-60

12V    –15 mV per amp 

–10 mV per amp

24V    –30 mV per amp 

–20 mV per amp

48V    –60 mV per amp 

–40 mV per amp

As an example, consider a 24V system using a TriStar-60 with a 30 amp load. 
The LVD will be reduced by 0.02V (per the table above) times 30 amps. This 
equals –0.6V. A DIP-switch selected LVD of 23.4V would be reduced to 22.8V 
in this example.

Note that the LEDs are linked to the LVD setting, so the LEDs are also current 
compensated.

c o n t i n u e d . . .

Содержание TriStar TS-45

Страница 1: ...peration and Maintenance Manual MAXIMUM POWER POINT TRACKING Solar Battery Charging Load Control Diversion Control For the most recent manual revisions see the version at www morningstarcorp com MODEL...

Страница 2: ...sh Installation 26 3 0 Operation 27 3 1 Operator s Tasks 27 3 2 Push button 27 3 3 LED Indications 28 3 4 Protections and Fault Recovery 29 3 5 Data Logging 32 3 6 Inspection and Maintenance 32 4 0 So...

Страница 3: ...ix 3 LED Indications 70 12 0 Certifications 73 co nt i nued IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important safety installation operating and mantenance instructio...

Страница 4: ...xposure to the elements and do not allow water to enter the controller Install the TriStar PWM in a location that prevents casual contact The TriStar PWM heatsink can become very hot during operation...

Страница 5: ...tain there is enough ventilation to release the gases Never smoke in the battery area If battery acid comes into contact with the skin wash with soap and water If the acid contacts the eye flood with...

Страница 6: ...rez vous que le niveau d lectrolyte de la batterie est correct avant de commencer la charge Ne tentez pas de charger une batterie gel e Recyclez la batterie quand elle est remplac e 1 0 TriStar Descri...

Страница 7: ...he enclosure can be grounded using the ground terminal in the wiring compartment The TriStar is protected from faults electronically with automatic recovery There are no fuses or mechanical parts insi...

Страница 8: ...nto an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help This Class B digital apparatus complies with Canadia...

Страница 9: ...70 amp res pour le TriStar PWM 45 et 90 amp res pour le TriStar PWM 60 M WARNING Installation must comply with all US National Electrical Code and Canadian Electrical Code requirements Breakers and fu...

Страница 10: ...ltage is the same as the nominal battery voltage Do not install a TriStar in a sealed compartment with batteries Never open the TriStar access cover unless both the solar and battery power has been di...

Страница 11: ...cated behind the negative power terminals Each switch is numbered The solar battery charging functions that can be adjusted with the DIP switches follow Control Mode Battery Charging 1 System Voltage...

Страница 12: ...ches Number 2 3 System Voltage Voltage Switch 2 Switch 3 Auto Off Off 12 Off On 24 On Off 48 On On Auto Select 1 2 3 4 5 6 7 8 DIP ON 12 Volts 1 2 3 4 5 6 7 8 DIP ON ON OFF 24 Volts 1 2 3 4 5 6 7 8 DI...

Страница 13: ...some types of telecom equipment or radios the TriStar can be converted to an On Off method of solar charge regulation It should be noted that the On Off solar charge regulation is much less effective...

Страница 14: ...0 56 Nm 5 in lb of torque The maximum length allowed for each battery voltage sense wire is 30 meters 98 ft The battery sense terminal has polarity Be careful to connect the battery positive terminal...

Страница 15: ...er NEC 690 45 A and NEC Table 250 122 minimum sizes for copper grounding wire are TS MPPT 45 10 AWG 5 mm2 TS MPPT 60 M 8 AWG 8 mm2 OR of the same or greater cross sectional area as the PV wires Connec...

Страница 16: ...rform However the operator should be familiar with the basic operation and care of the TriStar as described below 3 1 Operator s Tasks Use the push button as needed see 3 2 below Check the LEDs for st...

Страница 17: ...LVD 0 30V 0 60V 1 20V LVD 0 15V 0 30V 0 60V LVD The load status LEDs are determined by the LVD voltage plus the specified transition voltages As the battery voltage rises or falls each voltage transi...

Страница 18: ...polarity will be damaged Be very careful to connect loads to the controller with correct polarity See Section 5 4 DIP switch fault R Y G sequencing If a DIP switch is changed while there is power to t...

Страница 19: ...d instructions are available on our website 3 6 Inspection and Maintenance WARNING RISK OF ELECTRICAL SHOCK NO POWER OR ACCESSORY TERMINALS ARE ELECTRICALLY ISOLATED FROM DC INPUT AND MAY BE ENERGIZED...

Страница 20: ...troller to the battery is recommended This allows a precise battery voltage input to the controller and more accurate battery charging See Section 4 3 for more information Temperature Compensation All...

Страница 21: ...ing may go into PWM absorption almost every day If the battery temperature is colder the charging will begin to regulate too soon and the battery may not be recharged with a limited solar resource If...

Страница 22: ...ell drift Equalization cycles help to bring all the cells to the same voltage Mix the electrolyte In flooded batteries especially tall cells the heavier acid will fall to the bottom of the cell over t...

Страница 23: ...e to level individual cells This is not an equalization and will not vent gas from sealed batteries that require up to 14 4V charging 12V battery This boost charge for sealed cells allows for adjustab...

Страница 24: ...Battery 12V 24V 48V Switch LVD LVD LVD SOC LVDR LVDR LVDR off off off 11 1 22 2 44 4 8 12 6 25 2 50 4 off off on 11 3 22 6 45 2 12 12 8 25 6 51 2 off on off 11 5 23 0 46 0 18 13 0 26 0 52 0 off on on...

Страница 25: ...ivert excess current to an external load As the battery becomes fully charged the FET switches are closed for longer periods of time to direct more current to the diversion load As the battery charges...

Страница 26: ...on 4 3 Temperature Effects and Battery Voltage Sense 4 4 Equalization 4 5 Float 9 0 Battery Information 6 4 Selecting the Diversion Load It is critical that the diversion load be sized correctly If th...

Страница 27: ...for the same voltage as the system voltage Nominal Voltage TriStar 45 TriStar 60 48V 2700W at 60V 3600W at 60V 24V 1350W at 30V 1800W at 30V 12V 675W at 15V 900W at 15V These maximum power ratings ar...

Страница 28: ...leurs TriStar 6 6 Additional Information Visit Morningstar s website www morningstarcorp com for additional diversion charge control information The website provides expanded technical support for mo...

Страница 29: ...alert the user to an existing fault or alarm In this situation the LED indicators will flash a particular sequence Section 3 3 references these sequences with their associated faults and alarms Flash...

Страница 30: ...al support documents FAQs or to request technical support 9 0 Battery Information The standard battery charging programs in the TriStar controller as described in Section 4 2 are typical charging algo...

Страница 31: ...calcium with low internal losses and very low water consumption throughout their life Selenium plates also have poor cycling life Lead Antimony Antimony cells are rugged and provide long service life...

Страница 32: ...BUTOR AGENT OR EMPLOYEE IS AUTHORIZED TO MAKE ANY MODIFICATION OR EXTENSION TO THIS WARRANTY MORNINGSTAR IS NOT RESPONSIBLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND INCLUDING BUT NOT LIMITE...

Страница 33: ...rol DIP Settings The NOTE The DIP switches should be changed only when there is no power to the controller Turn off disconnect switches and remove power to the controller before changing a DIP switch...

Страница 34: ...ON Figure A1 3 Step 3 DIP Switches 2 3 The auto voltage selection occurs when the battery is connected and the TriStar starts up There should be no loads on the battery that might cause a discharged b...

Страница 35: ...Custom Settings Figure A1 5 Step 3 DIP Switch 4 5 6 Select one of the 7 standard Lighting Control algorithms or select the custom DIP switch for special custom settings using the PC software The defau...

Страница 36: ...ition With switches 1 and 7 in the ON position Diversion Charge Contol is set The OFF settings will operate as follows Switch Function 1 Must be ON to set Diversion Control 2 3 Auto voltage selected 4...

Страница 37: ...rsion Switch 7 On 1 2 3 4 5 6 7 8 DIP ON ON OFF Figure A2 5 Step 3 DIP Switch 7 In the Diversion Charge Control mode DIP switch 7 must be in the ON position DIP Switch Number 8 Battery Equalization Eq...

Страница 38: ...ond Float state G slow blink 1 second on 1 second off Battery State of Charge LED Indications when battery is charging G on 80 to 95 SOC G Y on 60 to 80 SOC Y on 35 to 60 SOC Y R on 0 to 35 SOC R on b...

Страница 39: ...ds for CE marking Immunity EN 61000 4 3 2006 EN 61000 4 6 2009 Emissions CISPR 22 2008 Safety EN60335 1 EN60335 2 29 battery chargers EN 62109 1 2010 TrisStarTM MeterBusTM are trademarks of Morningsta...

Отзывы: