background image

55

M O R N I N G S T A R   C O R P O R A T I O N

9.0

54

S E L F - T E S T I N G / D I A G N O S T I C S

8.2  Troubleshooting Solar Charging

 

•  Over-charging or under-charging the battery

 

•  DIP switch settings may be wrong 

 

•  RTS is not correcting for high or low temperatures

 

•  Over-temperature condition is reducing the charging current (heat sink 

cooling may be blocked — indicated with LEDs)

 

•  Voltage drop between TriStar and battery is too high 

(connect the battery 

voltage sense — see Section 2.3 Step 5)

 

•  Battery charging requires temperature compensation (connect a remote 

temperature sensor)

•  Load is too large and is discharging the battery

Not charging the battery

•  DIP switch settings may be wrong (check each switch position carefully)
•  TriStar has detected a fault 

(indicated by sequencing LEDS, refer to Section 3.3)

•  Solar circuit breaker or disconnect is open

 

•  Reversed polarity connections at the solar terminals (TriStar will not detect 

the solar array)

•  Short circuit in the solar array has eliminated part of the array output
•  Solar array is not providing enough current (low sun or fault in the array)

•  Battery is failing and cannot hold a charge

8.3  Troubleshooting Load Control

No power to the load

•  DIP switch settings may be wrong (check each switch position carefully)
•  Controller is in LVD (check the LEDs)
•  Load circuit breaker or disconnect may be open
•  Check the load cables for continuity and good connection

 

•  An over-temperature condition may have caused the load to be 

disconnected

8.4  Troubleshooting Diversion Control

•  Diversion load is too small so PWM reaches 99%
•  Diversion load is burned out so PWM reaches 99%
•  Diversion load is too large so TriStar faults on overcurrent

 

•  An overtemperature condition may have caused the load  

to be disconnected

• The RTS is not correcting for high or low temperatures
• Voltage drops between the TriStar and battery are too high

 

Still having problems? 

Point your web browser to http://www.

morningstarcorp.com for technical support documents,  
FAQs, or to request technical support.

9.0   Battery Information

The standard battery charging programs in the TriStar controller, as described 
in Section 4.2, are typical charging algorithms for three battery types:
• sealed (VRLA)
• flooded (vented)

• L-16 group

Other battery chemistries such as NiCad, or special voltages such as 36V, 
can be charged using a custom charging algorithm modified with the PC 
software. Only the standard TriStar battery charging programs will be 
discussed here.

 CAUTION: Never attempt to charge a primary (non-rechargeable) 

battery.

  

PRUDENCE : N’essayez jamais de charger une batterie primaire  

(non-rechargeable).

All charging voltages noted below will be for 12V batteries at 25˚C.

9.1  Sealed Batteries

The general class of sealed batteries suitable for solar systems are called 
VRLA (Valve Regulated Lead-Acid) batteries. The two main characteristics of 
VRLA batteries are electrolyte immobilization and oxygen recombination. As 
the battery recharges, gasing is limited and is recombined to minimize the 
loss of water.

The two types of VRLA batteries most often used in solar are AGM and Gel.

AGM:

Absorbed Glass Mat batteries are still considered to be a “wet cell” because 
the electrolyte is retained in fiberglass mats between the plates. Some newer 
AGM battery designs recommend constant voltage charging to 2.45 volts/cell 
(14.7V). For cycling applications, charging to 14.4V or 14.5V is often 
recommended.

AGM batteries are better suited to low discharge applications than daily 
cycling. These batteries should not be equalized since gasing can be vented 
which causes the battery to dry out. There is also a potential for thermal 
runaway if the battery gets too hot, and this will destroy the battery. AGM 
batteries are affected by heat, and can lose 50% of their service life for every 

8˚C (15˚F) over 25˚C (77˚F).

It is very important not to exceed the gas recombination capabilities of the AGM. 

The optimum charging temperature range is from 5 to 35˚C (40 to 95˚F).

Gel:

Gel batteries have characteristics similar to AGM, except a silica additive 
immobilizes the electrolyte to prevent leakage from the case. And like AGM, it 

Содержание TriStar TS-45

Страница 1: ...peration and Maintenance Manual MAXIMUM POWER POINT TRACKING Solar Battery Charging Load Control Diversion Control For the most recent manual revisions see the version at www morningstarcorp com MODEL...

Страница 2: ...sh Installation 26 3 0 Operation 27 3 1 Operator s Tasks 27 3 2 Push button 27 3 3 LED Indications 28 3 4 Protections and Fault Recovery 29 3 5 Data Logging 32 3 6 Inspection and Maintenance 32 4 0 So...

Страница 3: ...ix 3 LED Indications 70 12 0 Certifications 73 co nt i nued IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important safety installation operating and mantenance instructio...

Страница 4: ...xposure to the elements and do not allow water to enter the controller Install the TriStar PWM in a location that prevents casual contact The TriStar PWM heatsink can become very hot during operation...

Страница 5: ...tain there is enough ventilation to release the gases Never smoke in the battery area If battery acid comes into contact with the skin wash with soap and water If the acid contacts the eye flood with...

Страница 6: ...rez vous que le niveau d lectrolyte de la batterie est correct avant de commencer la charge Ne tentez pas de charger une batterie gel e Recyclez la batterie quand elle est remplac e 1 0 TriStar Descri...

Страница 7: ...he enclosure can be grounded using the ground terminal in the wiring compartment The TriStar is protected from faults electronically with automatic recovery There are no fuses or mechanical parts insi...

Страница 8: ...nto an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help This Class B digital apparatus complies with Canadia...

Страница 9: ...70 amp res pour le TriStar PWM 45 et 90 amp res pour le TriStar PWM 60 M WARNING Installation must comply with all US National Electrical Code and Canadian Electrical Code requirements Breakers and fu...

Страница 10: ...ltage is the same as the nominal battery voltage Do not install a TriStar in a sealed compartment with batteries Never open the TriStar access cover unless both the solar and battery power has been di...

Страница 11: ...cated behind the negative power terminals Each switch is numbered The solar battery charging functions that can be adjusted with the DIP switches follow Control Mode Battery Charging 1 System Voltage...

Страница 12: ...ches Number 2 3 System Voltage Voltage Switch 2 Switch 3 Auto Off Off 12 Off On 24 On Off 48 On On Auto Select 1 2 3 4 5 6 7 8 DIP ON 12 Volts 1 2 3 4 5 6 7 8 DIP ON ON OFF 24 Volts 1 2 3 4 5 6 7 8 DI...

Страница 13: ...some types of telecom equipment or radios the TriStar can be converted to an On Off method of solar charge regulation It should be noted that the On Off solar charge regulation is much less effective...

Страница 14: ...0 56 Nm 5 in lb of torque The maximum length allowed for each battery voltage sense wire is 30 meters 98 ft The battery sense terminal has polarity Be careful to connect the battery positive terminal...

Страница 15: ...er NEC 690 45 A and NEC Table 250 122 minimum sizes for copper grounding wire are TS MPPT 45 10 AWG 5 mm2 TS MPPT 60 M 8 AWG 8 mm2 OR of the same or greater cross sectional area as the PV wires Connec...

Страница 16: ...rform However the operator should be familiar with the basic operation and care of the TriStar as described below 3 1 Operator s Tasks Use the push button as needed see 3 2 below Check the LEDs for st...

Страница 17: ...LVD 0 30V 0 60V 1 20V LVD 0 15V 0 30V 0 60V LVD The load status LEDs are determined by the LVD voltage plus the specified transition voltages As the battery voltage rises or falls each voltage transi...

Страница 18: ...polarity will be damaged Be very careful to connect loads to the controller with correct polarity See Section 5 4 DIP switch fault R Y G sequencing If a DIP switch is changed while there is power to t...

Страница 19: ...d instructions are available on our website 3 6 Inspection and Maintenance WARNING RISK OF ELECTRICAL SHOCK NO POWER OR ACCESSORY TERMINALS ARE ELECTRICALLY ISOLATED FROM DC INPUT AND MAY BE ENERGIZED...

Страница 20: ...troller to the battery is recommended This allows a precise battery voltage input to the controller and more accurate battery charging See Section 4 3 for more information Temperature Compensation All...

Страница 21: ...ing may go into PWM absorption almost every day If the battery temperature is colder the charging will begin to regulate too soon and the battery may not be recharged with a limited solar resource If...

Страница 22: ...ell drift Equalization cycles help to bring all the cells to the same voltage Mix the electrolyte In flooded batteries especially tall cells the heavier acid will fall to the bottom of the cell over t...

Страница 23: ...e to level individual cells This is not an equalization and will not vent gas from sealed batteries that require up to 14 4V charging 12V battery This boost charge for sealed cells allows for adjustab...

Страница 24: ...Battery 12V 24V 48V Switch LVD LVD LVD SOC LVDR LVDR LVDR off off off 11 1 22 2 44 4 8 12 6 25 2 50 4 off off on 11 3 22 6 45 2 12 12 8 25 6 51 2 off on off 11 5 23 0 46 0 18 13 0 26 0 52 0 off on on...

Страница 25: ...ivert excess current to an external load As the battery becomes fully charged the FET switches are closed for longer periods of time to direct more current to the diversion load As the battery charges...

Страница 26: ...on 4 3 Temperature Effects and Battery Voltage Sense 4 4 Equalization 4 5 Float 9 0 Battery Information 6 4 Selecting the Diversion Load It is critical that the diversion load be sized correctly If th...

Страница 27: ...for the same voltage as the system voltage Nominal Voltage TriStar 45 TriStar 60 48V 2700W at 60V 3600W at 60V 24V 1350W at 30V 1800W at 30V 12V 675W at 15V 900W at 15V These maximum power ratings ar...

Страница 28: ...leurs TriStar 6 6 Additional Information Visit Morningstar s website www morningstarcorp com for additional diversion charge control information The website provides expanded technical support for mo...

Страница 29: ...alert the user to an existing fault or alarm In this situation the LED indicators will flash a particular sequence Section 3 3 references these sequences with their associated faults and alarms Flash...

Страница 30: ...al support documents FAQs or to request technical support 9 0 Battery Information The standard battery charging programs in the TriStar controller as described in Section 4 2 are typical charging algo...

Страница 31: ...calcium with low internal losses and very low water consumption throughout their life Selenium plates also have poor cycling life Lead Antimony Antimony cells are rugged and provide long service life...

Страница 32: ...BUTOR AGENT OR EMPLOYEE IS AUTHORIZED TO MAKE ANY MODIFICATION OR EXTENSION TO THIS WARRANTY MORNINGSTAR IS NOT RESPONSIBLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND INCLUDING BUT NOT LIMITE...

Страница 33: ...rol DIP Settings The NOTE The DIP switches should be changed only when there is no power to the controller Turn off disconnect switches and remove power to the controller before changing a DIP switch...

Страница 34: ...ON Figure A1 3 Step 3 DIP Switches 2 3 The auto voltage selection occurs when the battery is connected and the TriStar starts up There should be no loads on the battery that might cause a discharged b...

Страница 35: ...Custom Settings Figure A1 5 Step 3 DIP Switch 4 5 6 Select one of the 7 standard Lighting Control algorithms or select the custom DIP switch for special custom settings using the PC software The defau...

Страница 36: ...ition With switches 1 and 7 in the ON position Diversion Charge Contol is set The OFF settings will operate as follows Switch Function 1 Must be ON to set Diversion Control 2 3 Auto voltage selected 4...

Страница 37: ...rsion Switch 7 On 1 2 3 4 5 6 7 8 DIP ON ON OFF Figure A2 5 Step 3 DIP Switch 7 In the Diversion Charge Control mode DIP switch 7 must be in the ON position DIP Switch Number 8 Battery Equalization Eq...

Страница 38: ...ond Float state G slow blink 1 second on 1 second off Battery State of Charge LED Indications when battery is charging G on 80 to 95 SOC G Y on 60 to 80 SOC Y on 35 to 60 SOC Y R on 0 to 35 SOC R on b...

Страница 39: ...ds for CE marking Immunity EN 61000 4 3 2006 EN 61000 4 6 2009 Emissions CISPR 22 2008 Safety EN60335 1 EN60335 2 29 battery chargers EN 62109 1 2010 TrisStarTM MeterBusTM are trademarks of Morningsta...

Отзывы: