background image

46

D I V E R S I O N   C H A R G E   C O N T R O L

47

M O R N I N G S T A R   C O R P O R A T I O N

6.0

All values are @25ºC (77ºF).

  

A. B. C.  D.  E.  F.  G. 

  

 

 

Time  

    Max.

 

 

DIP 

PWM 

 

Until 

 

 Time 

Equalize 

Equalize 

  Switches 

Absorp. 

Float 

Float 

Equalization 

in Equal. 

Interval 

Cycle 

 (4-5-6) 

Voltage 

Voltage 

(hours) 

Voltage 

(hours) 

(days) 

(hours)

 off-off-off 

13.8 

13.6 

14.1 

28 

off-off-on 14.0  13.6 

14.3 

28 

off-on-off 14.2  13.6 

14.5 

28 

4

off-on-on 14.4  13.6 

14.7 

28 

4

on-off-off 14.6  13.7 

14.9 

28 

5

on-off-on 14.8  13.7 

15.1 

28 

5

on-on-off 15.0  13.7 

15.3 

28 

5

on-on-on   Custom   Custom    Custom

Table 6.1  Standard Diversion Charging Programs

A.   PWM Absorption Voltage

 - This is the PWM Absorption stage with 

constant voltage charging. The PWM absorption voltage is the maximum 
battery voltage that will be held constant.

B.   Float  Voltage

 - When the battery is fully charged, the charging voltage 

will be reduced to the float voltage for all diversion settings. The float 
voltage and transition values are adjustable with the PC software. 

C.   Time Until Float

 - This is the cumulative time in PWM before the battery 

voltage is reduced to the float voltage. If loads are present during the 
PWM absorption, the time to transition into float will be extended.

D.   Equalization  Voltage

 - During an equalization cycle, the charging voltage 

will be held constant at this voltage. Equalizations are manual, and can be 
selected for automatic 

(See Section 4.4.1)

.

E.   Time in Equalization

 - Charging at the selected equalization voltage will 

continue for this number of hours. 

F.   Equalization  Interval

 - Equalizations are typically done once a month. 

The cycles are 28 days so the equalization will begin on the same day of 
the week. Each new cycle will be reset as the equalization starts so that a 
28 day period will be maintained.

G.   Maximum Equalization Cycle

 - If the battery voltage cannot reach the 

equalization voltage, the equalization will terminate after this number of 
hours to avoid over gasing or heating the battery. If the battery requires 
more time in equalization, the manual push-button can be used to 
continue for one or more additional equalization cycles.

6.3.1  Battery Charging References

The diversion load battery charging is similar to conventional solar charging. 
Refer to the following sections in this manual for additional battery charging 
information.

4.1 

Four stages of charging (applies to diversion)

4.3 

Temperature Effects and Battery Voltage Sense 

4.4 Equalization
4.5 Float
9.0 

Battery Information

6.4  Selecting the Diversion Load

It is critical that the diversion load be sized correctly. If the load is too small, it 
cannot divert enough power from the source (wind, hydro, etc). The battery 
will continue charging and could be overcharged.

If the diversion load is too large, it will draw more current than the rating of the 
TriStar. The controller’s overload protection may disconnect the diversion 
load, and this will result in all of the source current going to the battery. 

  

CAUTION: The diversion load must be able to absorb the full power 

output of the source, but the load must never exceed the current rating 

of the TriStar controller. Otherwise, the battery can be overcharged and 

damaged.

  

PRUDENCE : La charge de diversion doit être capable d’absorber toute 

la puissance de sortie de la source, mais la charge ne doit jamais 

dépasser l’intensité nominale du contrôleur TriStar, pour ne pas 

surcharger et endommager la batterie.

6.4.1  Suitable Loads for Diversion

Water heating elements are commonly used for diversion load systems. 
These heating elements are reliable and widely available. Heating elements 
are also easy to replace, and the ratings are stable.

  

NOTE: Do not use light bulbs, motors, or other electrical devices for 

diversion loads. These loads will fail or cause the TriStar to disconnect 

the load. Only heating elements should be used.

  

REMARQUE : N’utilisez pas d’ampoules, de moteurs ou d’autres 

appareils électriques pour les charges de diversion. Ces charges ne 

fonctionneront pas ou provoqueront une déconnexion de la charge par 

le TriStar. Seuls les éléments de chauffe doivent être utilisés.

Water heating elements are typically 120 volts. Elements rated for 12, 24  
and 48 volts are also available, but more difficult to source. The de-rating  
for 120 volt heating elements is discussed in 6.4.3 below.

6.4.2  Definition of Terms

Maximum Source Current:

This is the maximum current output of all the energy sources (hydro, wind, 
solar, etc.) added together. This current will be diverted through the TriStar  
to the diversion load.

Maximum Battery Voltage:

This maximum voltage is the PWM regulation voltage selected with the DIP 
switches, plus the increase with an equalization, plus the increase due to 
lower temperatures. The highest battery voltage is commonly 15, 30 and  
60 volts for 12-, 24- and 48-volt systems.

Peak Load Current:

At the maximum battery voltage, this is the current the diversion load will 
draw. This peak load current must not exceed the TriStar’s rating.

Содержание TriStar TS-45

Страница 1: ...peration and Maintenance Manual MAXIMUM POWER POINT TRACKING Solar Battery Charging Load Control Diversion Control For the most recent manual revisions see the version at www morningstarcorp com MODEL...

Страница 2: ...sh Installation 26 3 0 Operation 27 3 1 Operator s Tasks 27 3 2 Push button 27 3 3 LED Indications 28 3 4 Protections and Fault Recovery 29 3 5 Data Logging 32 3 6 Inspection and Maintenance 32 4 0 So...

Страница 3: ...ix 3 LED Indications 70 12 0 Certifications 73 co nt i nued IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important safety installation operating and mantenance instructio...

Страница 4: ...xposure to the elements and do not allow water to enter the controller Install the TriStar PWM in a location that prevents casual contact The TriStar PWM heatsink can become very hot during operation...

Страница 5: ...tain there is enough ventilation to release the gases Never smoke in the battery area If battery acid comes into contact with the skin wash with soap and water If the acid contacts the eye flood with...

Страница 6: ...rez vous que le niveau d lectrolyte de la batterie est correct avant de commencer la charge Ne tentez pas de charger une batterie gel e Recyclez la batterie quand elle est remplac e 1 0 TriStar Descri...

Страница 7: ...he enclosure can be grounded using the ground terminal in the wiring compartment The TriStar is protected from faults electronically with automatic recovery There are no fuses or mechanical parts insi...

Страница 8: ...nto an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help This Class B digital apparatus complies with Canadia...

Страница 9: ...70 amp res pour le TriStar PWM 45 et 90 amp res pour le TriStar PWM 60 M WARNING Installation must comply with all US National Electrical Code and Canadian Electrical Code requirements Breakers and fu...

Страница 10: ...ltage is the same as the nominal battery voltage Do not install a TriStar in a sealed compartment with batteries Never open the TriStar access cover unless both the solar and battery power has been di...

Страница 11: ...cated behind the negative power terminals Each switch is numbered The solar battery charging functions that can be adjusted with the DIP switches follow Control Mode Battery Charging 1 System Voltage...

Страница 12: ...ches Number 2 3 System Voltage Voltage Switch 2 Switch 3 Auto Off Off 12 Off On 24 On Off 48 On On Auto Select 1 2 3 4 5 6 7 8 DIP ON 12 Volts 1 2 3 4 5 6 7 8 DIP ON ON OFF 24 Volts 1 2 3 4 5 6 7 8 DI...

Страница 13: ...some types of telecom equipment or radios the TriStar can be converted to an On Off method of solar charge regulation It should be noted that the On Off solar charge regulation is much less effective...

Страница 14: ...0 56 Nm 5 in lb of torque The maximum length allowed for each battery voltage sense wire is 30 meters 98 ft The battery sense terminal has polarity Be careful to connect the battery positive terminal...

Страница 15: ...er NEC 690 45 A and NEC Table 250 122 minimum sizes for copper grounding wire are TS MPPT 45 10 AWG 5 mm2 TS MPPT 60 M 8 AWG 8 mm2 OR of the same or greater cross sectional area as the PV wires Connec...

Страница 16: ...rform However the operator should be familiar with the basic operation and care of the TriStar as described below 3 1 Operator s Tasks Use the push button as needed see 3 2 below Check the LEDs for st...

Страница 17: ...LVD 0 30V 0 60V 1 20V LVD 0 15V 0 30V 0 60V LVD The load status LEDs are determined by the LVD voltage plus the specified transition voltages As the battery voltage rises or falls each voltage transi...

Страница 18: ...polarity will be damaged Be very careful to connect loads to the controller with correct polarity See Section 5 4 DIP switch fault R Y G sequencing If a DIP switch is changed while there is power to t...

Страница 19: ...d instructions are available on our website 3 6 Inspection and Maintenance WARNING RISK OF ELECTRICAL SHOCK NO POWER OR ACCESSORY TERMINALS ARE ELECTRICALLY ISOLATED FROM DC INPUT AND MAY BE ENERGIZED...

Страница 20: ...troller to the battery is recommended This allows a precise battery voltage input to the controller and more accurate battery charging See Section 4 3 for more information Temperature Compensation All...

Страница 21: ...ing may go into PWM absorption almost every day If the battery temperature is colder the charging will begin to regulate too soon and the battery may not be recharged with a limited solar resource If...

Страница 22: ...ell drift Equalization cycles help to bring all the cells to the same voltage Mix the electrolyte In flooded batteries especially tall cells the heavier acid will fall to the bottom of the cell over t...

Страница 23: ...e to level individual cells This is not an equalization and will not vent gas from sealed batteries that require up to 14 4V charging 12V battery This boost charge for sealed cells allows for adjustab...

Страница 24: ...Battery 12V 24V 48V Switch LVD LVD LVD SOC LVDR LVDR LVDR off off off 11 1 22 2 44 4 8 12 6 25 2 50 4 off off on 11 3 22 6 45 2 12 12 8 25 6 51 2 off on off 11 5 23 0 46 0 18 13 0 26 0 52 0 off on on...

Страница 25: ...ivert excess current to an external load As the battery becomes fully charged the FET switches are closed for longer periods of time to direct more current to the diversion load As the battery charges...

Страница 26: ...on 4 3 Temperature Effects and Battery Voltage Sense 4 4 Equalization 4 5 Float 9 0 Battery Information 6 4 Selecting the Diversion Load It is critical that the diversion load be sized correctly If th...

Страница 27: ...for the same voltage as the system voltage Nominal Voltage TriStar 45 TriStar 60 48V 2700W at 60V 3600W at 60V 24V 1350W at 30V 1800W at 30V 12V 675W at 15V 900W at 15V These maximum power ratings ar...

Страница 28: ...leurs TriStar 6 6 Additional Information Visit Morningstar s website www morningstarcorp com for additional diversion charge control information The website provides expanded technical support for mo...

Страница 29: ...alert the user to an existing fault or alarm In this situation the LED indicators will flash a particular sequence Section 3 3 references these sequences with their associated faults and alarms Flash...

Страница 30: ...al support documents FAQs or to request technical support 9 0 Battery Information The standard battery charging programs in the TriStar controller as described in Section 4 2 are typical charging algo...

Страница 31: ...calcium with low internal losses and very low water consumption throughout their life Selenium plates also have poor cycling life Lead Antimony Antimony cells are rugged and provide long service life...

Страница 32: ...BUTOR AGENT OR EMPLOYEE IS AUTHORIZED TO MAKE ANY MODIFICATION OR EXTENSION TO THIS WARRANTY MORNINGSTAR IS NOT RESPONSIBLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND INCLUDING BUT NOT LIMITE...

Страница 33: ...rol DIP Settings The NOTE The DIP switches should be changed only when there is no power to the controller Turn off disconnect switches and remove power to the controller before changing a DIP switch...

Страница 34: ...ON Figure A1 3 Step 3 DIP Switches 2 3 The auto voltage selection occurs when the battery is connected and the TriStar starts up There should be no loads on the battery that might cause a discharged b...

Страница 35: ...Custom Settings Figure A1 5 Step 3 DIP Switch 4 5 6 Select one of the 7 standard Lighting Control algorithms or select the custom DIP switch for special custom settings using the PC software The defau...

Страница 36: ...ition With switches 1 and 7 in the ON position Diversion Charge Contol is set The OFF settings will operate as follows Switch Function 1 Must be ON to set Diversion Control 2 3 Auto voltage selected 4...

Страница 37: ...rsion Switch 7 On 1 2 3 4 5 6 7 8 DIP ON ON OFF Figure A2 5 Step 3 DIP Switch 7 In the Diversion Charge Control mode DIP switch 7 must be in the ON position DIP Switch Number 8 Battery Equalization Eq...

Страница 38: ...ond Float state G slow blink 1 second on 1 second off Battery State of Charge LED Indications when battery is charging G on 80 to 95 SOC G Y on 60 to 80 SOC Y on 35 to 60 SOC Y R on 0 to 35 SOC R on b...

Страница 39: ...ds for CE marking Immunity EN 61000 4 3 2006 EN 61000 4 6 2009 Emissions CISPR 22 2008 Safety EN60335 1 EN60335 2 29 battery chargers EN 62109 1 2010 TrisStarTM MeterBusTM are trademarks of Morningsta...

Отзывы: