background image

45

M O R N I N G S T A R   C O R P O R A T I O N

6.0

44

L O A D   C O N T R O L

After an LVD, the load reconnect voltages are 0.25 volts per battery cell 
higher than the LVD (for example, in a 12V system the LVD

R

 would be 1.5 

volts above LVD). Battery voltages can rise quickly after an LVD, typically from 
1.0 to 1.3 volts or more (12V system). The LVD

R

 value must be high enough to 

avoid cycling in and out of LVD.

5.3  LVD Warning

When the battery is discharging and the green LED changes to the next state 
(G-Y LEDs on), there are four remaining transitions to LVD (refer to the LED 
indications in Section 3.3). Each of these LED displays will serve as a 
warning of an approaching LVD. The final warning is a blinking red LED state.

The amount of time from the initial G-Y display until the load disconnect will 
depend on many factors. These include:

•  The rate of discharge.   

• The health of the battery    

• The LVD setting

For a “typical” system with a healthy battery and an LVD setting of about 11.7 
volts, there could be approximately 10 hours per LED transition. The LVD 
would occur about 40 hours from the first G-Y display (under constant load 
with no charging).

Another significant factor affecting the warning time is the LVD voltage 
setpoint. Lower LVD voltage settings may result in the battery discharging 
70% or 80% of its capacity. In this case, the battery’s very low charge state 
will result in the voltage dropping much faster. At the lowest LVD settings, 
there could be as little as 2 or 3 hours of warning between LED transitions  
for a healthy battery.

The amount of time it takes to transition through the LEDs to LVD can vary 
greatly for different systems. It may be worthwhile to measure the time it takes 
for your system to transition from one LED state to the next. Do this under 
“typical” discharging loads. 

This will provide a good reference for how long it will take for your system  
to reach LVD. It can also provide a benchmark for judging the health of your 
battery over time.

6.0  Diversion Charge Control 

The TriStar’s third mode of operation is diversion load battery charge control. 
As the battery becomes fully charged, the TriStar will divert excess current 
from the battery to a dedicated diversion load. This diversion load must be 
large enough to absorb all the excess energy, but not too large to cause a 
controller overload condition.

6.1  Diversion Charge Control

In the diversion mode, the TriStar will use PWM charging regulation to divert 
excess current to an external load. As the battery becomes fully charged, the 
FET switches are closed for longer periods of time to direct more current to 
the diversion load. 

As the battery charges, the diversion duty cycle will increase. When fully 
charged, all the source energy will flow into the diversion load if there are  
no other loads. The generating source is typically a wind or hydro generator. 
Some solar systems also use diversion to heat water rather than open the 
solar array and lose the energy.

The most important factor for successful diversion charge control is the 
correct sizing of the diversion load. If too large, the controller’s protections 
may open the FET switches and stop diverting current from the battery. This 
condition can damage the battery.

If you are not confident and certain about the installation, a professional 
installation by your dealer is recommended.

6.2  Diversion Current Ratings

The maximum diversion load current capability for the two TriStar versions is 
45 amps (TS-45) and 60 amps (TS-60/M). The diversion loads must be sized 
so that the peak load current cannot exceed these maximum ratings.

See section 6.4 below for selecting and sizing the diversion loads.

The total current for all combined charging sources (wind, hydro, solar) should 
be equal or less than two-thirds of the controller’s current rating: 30A (TS-45) 
and 40A (TS-60/M). This limit will provide a required margin for high winds 
and high water flow rates as well as a margin for error in the rating and 
selection of the diversion load. This protects against an overload and a safety 
disconnect in the TriStar controller, which would leave the battery charging 
unregulated.

  

CAUTION: If the TriStar’s rating is exceeded and the controller dis-

connects the diversion load, Morningstar will not be responsible for 

any damage resulting to the system battery or other system compo-

nents. Refer to Morningstar’s Limited Warranty in Section 10.0.

  

PRUDENCE : Si la capacité du TriStar est dépassée et que le contrôleur 

déconnecte la charge de diversion, Morningstar ne sera pas responsable 

de tout dommage résultant de la batterie du système ou d’autres 

composants du système. Reportez-vous à la Garantie limitée de 

Morningstar dans la Section 10.0.

6.3  Standard Diversion Battery Charging Programs

The TriStar provides 7 standard diversion charging algorithms (programs) that 
are selected with the DIP switches. An 8th algorithm can be used for custom 
set-points using the PC software.

The table below summarizes the major parameters of the standard diversion 
battery charging algorithms. Note that all the voltages are for 12V systems 
(24V = 2X, 48V = 4X).

Содержание TriStar TS-45

Страница 1: ...peration and Maintenance Manual MAXIMUM POWER POINT TRACKING Solar Battery Charging Load Control Diversion Control For the most recent manual revisions see the version at www morningstarcorp com MODEL...

Страница 2: ...sh Installation 26 3 0 Operation 27 3 1 Operator s Tasks 27 3 2 Push button 27 3 3 LED Indications 28 3 4 Protections and Fault Recovery 29 3 5 Data Logging 32 3 6 Inspection and Maintenance 32 4 0 So...

Страница 3: ...ix 3 LED Indications 70 12 0 Certifications 73 co nt i nued IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important safety installation operating and mantenance instructio...

Страница 4: ...xposure to the elements and do not allow water to enter the controller Install the TriStar PWM in a location that prevents casual contact The TriStar PWM heatsink can become very hot during operation...

Страница 5: ...tain there is enough ventilation to release the gases Never smoke in the battery area If battery acid comes into contact with the skin wash with soap and water If the acid contacts the eye flood with...

Страница 6: ...rez vous que le niveau d lectrolyte de la batterie est correct avant de commencer la charge Ne tentez pas de charger une batterie gel e Recyclez la batterie quand elle est remplac e 1 0 TriStar Descri...

Страница 7: ...he enclosure can be grounded using the ground terminal in the wiring compartment The TriStar is protected from faults electronically with automatic recovery There are no fuses or mechanical parts insi...

Страница 8: ...nto an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help This Class B digital apparatus complies with Canadia...

Страница 9: ...70 amp res pour le TriStar PWM 45 et 90 amp res pour le TriStar PWM 60 M WARNING Installation must comply with all US National Electrical Code and Canadian Electrical Code requirements Breakers and fu...

Страница 10: ...ltage is the same as the nominal battery voltage Do not install a TriStar in a sealed compartment with batteries Never open the TriStar access cover unless both the solar and battery power has been di...

Страница 11: ...cated behind the negative power terminals Each switch is numbered The solar battery charging functions that can be adjusted with the DIP switches follow Control Mode Battery Charging 1 System Voltage...

Страница 12: ...ches Number 2 3 System Voltage Voltage Switch 2 Switch 3 Auto Off Off 12 Off On 24 On Off 48 On On Auto Select 1 2 3 4 5 6 7 8 DIP ON 12 Volts 1 2 3 4 5 6 7 8 DIP ON ON OFF 24 Volts 1 2 3 4 5 6 7 8 DI...

Страница 13: ...some types of telecom equipment or radios the TriStar can be converted to an On Off method of solar charge regulation It should be noted that the On Off solar charge regulation is much less effective...

Страница 14: ...0 56 Nm 5 in lb of torque The maximum length allowed for each battery voltage sense wire is 30 meters 98 ft The battery sense terminal has polarity Be careful to connect the battery positive terminal...

Страница 15: ...er NEC 690 45 A and NEC Table 250 122 minimum sizes for copper grounding wire are TS MPPT 45 10 AWG 5 mm2 TS MPPT 60 M 8 AWG 8 mm2 OR of the same or greater cross sectional area as the PV wires Connec...

Страница 16: ...rform However the operator should be familiar with the basic operation and care of the TriStar as described below 3 1 Operator s Tasks Use the push button as needed see 3 2 below Check the LEDs for st...

Страница 17: ...LVD 0 30V 0 60V 1 20V LVD 0 15V 0 30V 0 60V LVD The load status LEDs are determined by the LVD voltage plus the specified transition voltages As the battery voltage rises or falls each voltage transi...

Страница 18: ...polarity will be damaged Be very careful to connect loads to the controller with correct polarity See Section 5 4 DIP switch fault R Y G sequencing If a DIP switch is changed while there is power to t...

Страница 19: ...d instructions are available on our website 3 6 Inspection and Maintenance WARNING RISK OF ELECTRICAL SHOCK NO POWER OR ACCESSORY TERMINALS ARE ELECTRICALLY ISOLATED FROM DC INPUT AND MAY BE ENERGIZED...

Страница 20: ...troller to the battery is recommended This allows a precise battery voltage input to the controller and more accurate battery charging See Section 4 3 for more information Temperature Compensation All...

Страница 21: ...ing may go into PWM absorption almost every day If the battery temperature is colder the charging will begin to regulate too soon and the battery may not be recharged with a limited solar resource If...

Страница 22: ...ell drift Equalization cycles help to bring all the cells to the same voltage Mix the electrolyte In flooded batteries especially tall cells the heavier acid will fall to the bottom of the cell over t...

Страница 23: ...e to level individual cells This is not an equalization and will not vent gas from sealed batteries that require up to 14 4V charging 12V battery This boost charge for sealed cells allows for adjustab...

Страница 24: ...Battery 12V 24V 48V Switch LVD LVD LVD SOC LVDR LVDR LVDR off off off 11 1 22 2 44 4 8 12 6 25 2 50 4 off off on 11 3 22 6 45 2 12 12 8 25 6 51 2 off on off 11 5 23 0 46 0 18 13 0 26 0 52 0 off on on...

Страница 25: ...ivert excess current to an external load As the battery becomes fully charged the FET switches are closed for longer periods of time to direct more current to the diversion load As the battery charges...

Страница 26: ...on 4 3 Temperature Effects and Battery Voltage Sense 4 4 Equalization 4 5 Float 9 0 Battery Information 6 4 Selecting the Diversion Load It is critical that the diversion load be sized correctly If th...

Страница 27: ...for the same voltage as the system voltage Nominal Voltage TriStar 45 TriStar 60 48V 2700W at 60V 3600W at 60V 24V 1350W at 30V 1800W at 30V 12V 675W at 15V 900W at 15V These maximum power ratings ar...

Страница 28: ...leurs TriStar 6 6 Additional Information Visit Morningstar s website www morningstarcorp com for additional diversion charge control information The website provides expanded technical support for mo...

Страница 29: ...alert the user to an existing fault or alarm In this situation the LED indicators will flash a particular sequence Section 3 3 references these sequences with their associated faults and alarms Flash...

Страница 30: ...al support documents FAQs or to request technical support 9 0 Battery Information The standard battery charging programs in the TriStar controller as described in Section 4 2 are typical charging algo...

Страница 31: ...calcium with low internal losses and very low water consumption throughout their life Selenium plates also have poor cycling life Lead Antimony Antimony cells are rugged and provide long service life...

Страница 32: ...BUTOR AGENT OR EMPLOYEE IS AUTHORIZED TO MAKE ANY MODIFICATION OR EXTENSION TO THIS WARRANTY MORNINGSTAR IS NOT RESPONSIBLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND INCLUDING BUT NOT LIMITE...

Страница 33: ...rol DIP Settings The NOTE The DIP switches should be changed only when there is no power to the controller Turn off disconnect switches and remove power to the controller before changing a DIP switch...

Страница 34: ...ON Figure A1 3 Step 3 DIP Switches 2 3 The auto voltage selection occurs when the battery is connected and the TriStar starts up There should be no loads on the battery that might cause a discharged b...

Страница 35: ...Custom Settings Figure A1 5 Step 3 DIP Switch 4 5 6 Select one of the 7 standard Lighting Control algorithms or select the custom DIP switch for special custom settings using the PC software The defau...

Страница 36: ...ition With switches 1 and 7 in the ON position Diversion Charge Contol is set The OFF settings will operate as follows Switch Function 1 Must be ON to set Diversion Control 2 3 Auto voltage selected 4...

Страница 37: ...rsion Switch 7 On 1 2 3 4 5 6 7 8 DIP ON ON OFF Figure A2 5 Step 3 DIP Switch 7 In the Diversion Charge Control mode DIP switch 7 must be in the ON position DIP Switch Number 8 Battery Equalization Eq...

Страница 38: ...ond Float state G slow blink 1 second on 1 second off Battery State of Charge LED Indications when battery is charging G on 80 to 95 SOC G Y on 60 to 80 SOC Y on 35 to 60 SOC Y R on 0 to 35 SOC R on b...

Страница 39: ...ds for CE marking Immunity EN 61000 4 3 2006 EN 61000 4 6 2009 Emissions CISPR 22 2008 Safety EN60335 1 EN60335 2 29 battery chargers EN 62109 1 2010 TrisStarTM MeterBusTM are trademarks of Morningsta...

Отзывы: