How To Adjust Start
Chapter Six: Operation in Tuning Mode
166
How To Adjust Start
MANUAL
TORR
TUNING
START
LEFT DISPLAY
CENTER DISPLAY
RIGHT DISPLAY
This is the current valve
position expressed as a
percent of the valve
control signal output.
This example shows a
setting of 20.1% of the
valve control signal
output.
The START valve position
is expressed as a percent
of the valve control signal
output.
In this example, START is
the parameter which is
selected for editing, and
is currently set at 25.5%.
This indicates which of the
four possible recipes is
selected for editing (in this
case, it is recipe 2).
MAIN DISPLAY
This is the pressure reading from the
gauge on the control channel.
Figure 47: Adjusting the Start Valve Position
Start is a valve position, expressed as a percent of the valve control signal output. The Start
value is used to set the initial position of the valve when the
AUTO
feature is evoked in Control
Mode. The Start value only applies if the valve was at full open or full close just prior to
evoking the
AUTO
feature.
Note
If the Softstart parameter (Code 13x in the Operation in Setup Mode
chapter), is enabled, it can override the Start parameter.
1. Repeatedly press the [
DISPLAY MODE
] key until the 146 unit is in Tuning Mode.
The system responds by scrolling through modes.