18 - 16
18. GOT MULTI-DROP CONNECTION
18.4 Connection Diagram
Precautions when preparing a cable
(1) Cable
Use a shielded twisted pair cable of 0.3mm
2
or more as
a cable for GOT multi-drop connection.The following
shows recommended model names and manufacturers
of the cable to be used.
(2) Cable for converting D-sub9 pin connector to
terminal block
Create by yourself, referring to the following connection
diagram.
Make sure to connect the wiring branched on the GOT side
connector.
Use a shielded twisted pair cable of 0.2mm
2
or more.
Use an applicable cable to D-sub connector.
Wiring should be the shortest distance.
(3) GOT side connector
For the GOT side connector, refer to the following.
1.4.1 GOT connector specifications
Connecting terminating resistors
When connecting a Serial Multi-Drop Connection Unit
to the GOT, a terminating resistor must be connected to
the GOT.
Set the terminating resistor setting switch to "Disable".
For the procedure to set the terminating resistor, refer
to the following.
1.4.3 Terminating resistors of GOT
Manufacturer
Model
Remark
Mitsubishi Cable
Industries,Ltd
SPEV(SB)-0.5-2P
Two-pair cable of
0.5mm
2
Showa Electric Wire &
Cable Co.,Ltd
KMPEV-SB
CWS-178 0.5SQ
2P
Two-pair cable of
0.5mm
2
Sumitomo Electric
Industries.,Ltd
DPEV SB 0.3
3P
Three-pair cable of
0.3mm
2
DPEV SB 0.5
3P
Three-pair cable of
0.5mm
2
The Furukawa Electric
Co.,Ltd
D-KPEV-SB 0.5
3P
Three-pair cable of
0.5mm
2
Fujikura Ltd.
IPEV-SB 2P
0.3 mm
2
Two-pair cable of
0.3mm
2
IPEV-SB 2P
0.5 mm
2
Two-pair cable of
0.5mm
2
Pair
Shield
Two-pair cable structural
drawing example
Three-pair cable structural
drawing example
Example of connection diagram for 2 pair wiring
SDA1
SDB1
RDA1
RDB1
SDA2
SDB2
RDA2
RDB2
SG
FG
SDA
SDB
RDA
RDB
SG
RSA
RSB
CSA
CSB
FG
1
6
2
7
5
3
8
4
9
Shell
Содержание GOT2000 Series
Страница 2: ......
Страница 62: ...1 38 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Страница 64: ......
Страница 80: ...2 16 2 DEVICE RANGE THAT CAN BE SET 2 6 MELSEC WS ...
Страница 246: ...7 26 7 COMPUTER LINK CONNECTION 7 6 Precautions ...
Страница 252: ...8 6 8 BUS CONNECTION 8 1 Connectable Model List ...
Страница 256: ...8 10 8 BUS CONNECTION 8 2 System Configuration ...
Страница 288: ...8 42 8 BUS CONNECTION 8 4 Precautions ...
Страница 324: ...9 36 9 MELSECNET H CONNECTION PLC TO PLC NETWORK MELSECNET 10 CONNECTION PLC TO PLC NETWORK ...
Страница 416: ......
Страница 510: ...15 46 15 SERVO AMPLIFIER CONNECTION 15 7 Precautions ...
Страница 518: ...16 8 16 ROBOT CONTROLLER CONNECTION 16 6 Precautions ...
Страница 540: ...17 22 17 CNC CONNECTION 17 7 Precautions ...
Страница 541: ...MULTIPLE GOT CONNECTIONS 18 GOT MULTI DROP CONNECTION 18 1 ...
Страница 542: ......
Страница 567: ...MULTI CHANNEL FUNCTION 19 MULTI CHANNEL FUNCTION 19 1 ...
Страница 568: ......
Страница 592: ...19 24 19 MULTI CHANNEL FUNCTION 19 3 GOT Side Settings Example Setting example for Ethernet connection 4 channels ...
Страница 599: ...FA TRANSPARENT FUNCTION 20 FA TRANSPARENT FUNCTION 20 1 ...
Страница 600: ......
Страница 668: ...20 68 20 FA TRANSPARENT FUNCTION 20 7 Precautions ...
Страница 670: ...REVISIONS 2 ...
Страница 673: ......