12 - 16
12. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
12.4 PLC Side Setting
[Controller Setting] of GT Designer3
POINT
POINT
POINT
[Controller Setting] of GT Designer3
For the setting method of [Controller Setting] of GT
Designer3, refer to the following.
12.3.1 Setting communication interface
(Communication settings)
12.4.2 Connecting to CC-Link
module (Q Series) with Ver.2
compatible
This section describes the settings of the GOT and CC-
Link module (Q Series) in the following case of system
configuration.
POINT
POINT
POINT
CC-Link module (Q Series)
For details of the CC-Link module (Q Series), refer to
the following manual.
CC-Link System Master/Local Module User's
Manual QJ61BT11N
System configuration
*1
The CC-Link module is mounted on the base unit slot 0.
The Start I/O No. of the CC-Link module is set to "0"
POINT
POINT
POINT
When connecting to Q170MCPU or Q170MSCPU(-S1)
When connected to Q170MCPU or Q170MSCPU(-
S1), the start I/O No. of the CC-Link module is set to
"70".
Item
Set value
Station No.
1: Station No.1
Transmission Rate
0: Online 156kbps
Mode
Ver.1: Remote net (Ver.1 mode)
Expanded Cyclic
Single (Use default value)
Number of stations occupied
1 Station
Input for Error Station
0: Clear
Retry
3times (Use default value)
Timeout Time
3sec (Use default value)
Delay Time
0ms (Use default value)
<CC-Link module>
*1
Type
: Master station
Station No.
: Station No.0
Mode
: Remote net (Ver.2 mode)
All connect count
: 1
Transmission speed : 156kbps
<GOT>
(Use the default value for settings other
than the following.)
Station type
: Intelligent device
station
Station No.
: Station No.1
Expanded cyclic setting : Single
Number of
stations occupied
: Exclusive station 1
Transmission speed
: 156kbps
(Use the default value for the settings other than the following.)
■
[Communication settings] of GT Designer3
■
Switch setting of CC-Link module (Q Series)
■
Содержание GOT2000 Series
Страница 2: ......
Страница 62: ...1 38 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Страница 64: ......
Страница 80: ...2 16 2 DEVICE RANGE THAT CAN BE SET 2 6 MELSEC WS ...
Страница 246: ...7 26 7 COMPUTER LINK CONNECTION 7 6 Precautions ...
Страница 252: ...8 6 8 BUS CONNECTION 8 1 Connectable Model List ...
Страница 256: ...8 10 8 BUS CONNECTION 8 2 System Configuration ...
Страница 288: ...8 42 8 BUS CONNECTION 8 4 Precautions ...
Страница 324: ...9 36 9 MELSECNET H CONNECTION PLC TO PLC NETWORK MELSECNET 10 CONNECTION PLC TO PLC NETWORK ...
Страница 416: ......
Страница 510: ...15 46 15 SERVO AMPLIFIER CONNECTION 15 7 Precautions ...
Страница 518: ...16 8 16 ROBOT CONTROLLER CONNECTION 16 6 Precautions ...
Страница 540: ...17 22 17 CNC CONNECTION 17 7 Precautions ...
Страница 541: ...MULTIPLE GOT CONNECTIONS 18 GOT MULTI DROP CONNECTION 18 1 ...
Страница 542: ......
Страница 567: ...MULTI CHANNEL FUNCTION 19 MULTI CHANNEL FUNCTION 19 1 ...
Страница 568: ......
Страница 592: ...19 24 19 MULTI CHANNEL FUNCTION 19 3 GOT Side Settings Example Setting example for Ethernet connection 4 channels ...
Страница 599: ...FA TRANSPARENT FUNCTION 20 FA TRANSPARENT FUNCTION 20 1 ...
Страница 600: ......
Страница 668: ...20 68 20 FA TRANSPARENT FUNCTION 20 7 Precautions ...
Страница 670: ...REVISIONS 2 ...
Страница 673: ......