12. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
12.4 PLC Side Setting
12 - 25
CC-Link CON
N
ECTION
(IN
T
ELLIGENT DEVIC
E ST
A
T
ION)
12
12.4.5
Connecting to MELSEC-L
series with CC-Link Ver.2
compatible
This section describes the settings of the GOT and
MELSEC-L in the following case of the system
configuration.
POINT
POINT
POINT
(1) CC-Link module (L Series)
For details of the CC-Link module (L Series), refer
to the following manual.
MELSEC-L CC-Link System Master/Local
Module User's Manual
(2) CC-Link function built-in CPU
For details on the CC-Link function built-in CPU,
refer to the following manual.
MELSEC-L CC-Link System Master/Local
Module User's Manual
System configuration
(Example when using CC-Link module (L Series))
[Network parameter] of GX Developer
(1) Network parameter
: Necessary
: As necessary
: Not necessary
*1
Set the Start I/O No. of the CC-Link module according to the
system configuration.
<CC-Link module>
*1
Type
: Master station
Station No.
: Station No.0
Mode
: Remote net (Ver.3 mode)
All connect count
: 1
Transmission speed : 156kbps
<GOT>
(Use the default value for settings other
than the following.)
Station type
: Intelligent device
station
Station No.
: Station No.1
Expanded cyclic setting : Single
Number of
stations occupied
: Exclusive station
Transmission speed
: 156kbps
(Use the default value for the settings other than the following.)
■
[Controller Setting] of GT Designer3
■
[Network parameter] of GX Developer
Item
Set value
Setting
necessity at
GOT
connection
No. of boards in module
1
Start I/O No.
*1
0000
H
Operation setting
(Use default value)
Type
Master station (fixed)
Mode
Remote net
(Ver.2 mode)
All connect count
1
Remote input (RX)
X400
Remote output (RY)
Y400
Remote register (RWr)
D300
Remote register (RWw)
D200
Special relay (SB)
SB0
Special register (SW)
SW0
Retry count
(Use default value)
Automatic reconnection
station count
Stand by master station No.
PLC down select
Scan mode setting
Delay information setting
Station information setting
Refer to (2)
Remote device station initial
setting
(Use default value)
Interrupt setting
Содержание GOT2000 Series
Страница 2: ......
Страница 62: ...1 38 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Страница 64: ......
Страница 80: ...2 16 2 DEVICE RANGE THAT CAN BE SET 2 6 MELSEC WS ...
Страница 246: ...7 26 7 COMPUTER LINK CONNECTION 7 6 Precautions ...
Страница 252: ...8 6 8 BUS CONNECTION 8 1 Connectable Model List ...
Страница 256: ...8 10 8 BUS CONNECTION 8 2 System Configuration ...
Страница 288: ...8 42 8 BUS CONNECTION 8 4 Precautions ...
Страница 324: ...9 36 9 MELSECNET H CONNECTION PLC TO PLC NETWORK MELSECNET 10 CONNECTION PLC TO PLC NETWORK ...
Страница 416: ......
Страница 510: ...15 46 15 SERVO AMPLIFIER CONNECTION 15 7 Precautions ...
Страница 518: ...16 8 16 ROBOT CONTROLLER CONNECTION 16 6 Precautions ...
Страница 540: ...17 22 17 CNC CONNECTION 17 7 Precautions ...
Страница 541: ...MULTIPLE GOT CONNECTIONS 18 GOT MULTI DROP CONNECTION 18 1 ...
Страница 542: ......
Страница 567: ...MULTI CHANNEL FUNCTION 19 MULTI CHANNEL FUNCTION 19 1 ...
Страница 568: ......
Страница 592: ...19 24 19 MULTI CHANNEL FUNCTION 19 3 GOT Side Settings Example Setting example for Ethernet connection 4 channels ...
Страница 599: ...FA TRANSPARENT FUNCTION 20 FA TRANSPARENT FUNCTION 20 1 ...
Страница 600: ......
Страница 668: ...20 68 20 FA TRANSPARENT FUNCTION 20 7 Precautions ...
Страница 670: ...REVISIONS 2 ...
Страница 673: ......