12. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
12.4 PLC Side Setting
12 - 19
CC-Link CON
N
ECTION
(IN
T
ELLIGENT DEVIC
E ST
A
T
ION)
12
: Necessary
: As necessary
: Not necessary
*1
When the [Mode] of the CC-Link module is set at [Remote
net - (Ver. 2 mode)], [Remote station points] can be set.
[Remote station points] is a setting for the remote I/O station.
The default value (32 points) must be used on the GOT.
*2
Set the same setting as that of the GOT.
POINT
POINT
POINT
When changing the network parameter
After writing the network parameter to the C Controller
module, either turn the C Controller module OFF and
then ON or reset it.
[Communication settings] of GT Designer3
POINT
POINT
POINT
[Controller Setting] of GT Designer3
For the setting method of [Controller Setting] of GT
Designer3, refer to the following.
12.3.1 Setting communication interface
(Communication settings)
Op
erat
ion set
tin
gs
Type
Master station
Mode
Remote net
(Ver.2 mode)
Expanded cyclic setting
Single
Occupied number
Exclusive station 1
Error event: input data
status
Clear
CPU stop: data link status
Refresh
Other settings
(Use default value)
S
tat
ion inf
orma
tio
n se
tt
ings
All connect count
1
Station Type
Sta.
No.1
Ver.2 intelligent device
station
Expanded cyclic
setting
*2
Sta.
No.1
Single
Occupied number
*2
Sta.
No.1
Exclusive station 1
Remote station points
Sta.
No.1
32 points
Reserve/invalid
station select
Sta.
No.1
No setting
Intelligent buffer select
(word)
(Use default value)
Item
*1
Set value
Setting
necessity at
GOT
connection
Item
Set value
Station No.
1: Station No.1
Transmission Rate
0: Online 156kbps
Mode
Ver.2: Remote net (Ver.2 mode)
Expanded Cyclic
Single
Number of stations occupied
1 Station
Input for Error Station
Clear
Retry
3times (Use default value)
Timeout Time
3sec (Use default value)
Delay Time
0ms (Use default value)
Содержание GOT2000 Series
Страница 2: ......
Страница 62: ...1 38 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Страница 64: ......
Страница 80: ...2 16 2 DEVICE RANGE THAT CAN BE SET 2 6 MELSEC WS ...
Страница 246: ...7 26 7 COMPUTER LINK CONNECTION 7 6 Precautions ...
Страница 252: ...8 6 8 BUS CONNECTION 8 1 Connectable Model List ...
Страница 256: ...8 10 8 BUS CONNECTION 8 2 System Configuration ...
Страница 288: ...8 42 8 BUS CONNECTION 8 4 Precautions ...
Страница 324: ...9 36 9 MELSECNET H CONNECTION PLC TO PLC NETWORK MELSECNET 10 CONNECTION PLC TO PLC NETWORK ...
Страница 416: ......
Страница 510: ...15 46 15 SERVO AMPLIFIER CONNECTION 15 7 Precautions ...
Страница 518: ...16 8 16 ROBOT CONTROLLER CONNECTION 16 6 Precautions ...
Страница 540: ...17 22 17 CNC CONNECTION 17 7 Precautions ...
Страница 541: ...MULTIPLE GOT CONNECTIONS 18 GOT MULTI DROP CONNECTION 18 1 ...
Страница 542: ......
Страница 567: ...MULTI CHANNEL FUNCTION 19 MULTI CHANNEL FUNCTION 19 1 ...
Страница 568: ......
Страница 592: ...19 24 19 MULTI CHANNEL FUNCTION 19 3 GOT Side Settings Example Setting example for Ethernet connection 4 channels ...
Страница 599: ...FA TRANSPARENT FUNCTION 20 FA TRANSPARENT FUNCTION 20 1 ...
Страница 600: ......
Страница 668: ...20 68 20 FA TRANSPARENT FUNCTION 20 7 Precautions ...
Страница 670: ...REVISIONS 2 ...
Страница 673: ......