95
-
'14 • SR-T-157
10.2 FDTC series
10.2.1 Diagnosing of microcomputer circuit
(1) Selfdiagnosis function
(a) Check indicator table
Whether a failure exists or not on the indoor unit can be know by the contents of remote control error code, indoor
unit green LED (power pilot lamp and microcomputer normality pilot lamp) or red LED (check pilot lamp).
(i) Indoor unit
Remote control
Indoor control PCB
Location of trouble
Description of trouble
Repair method
Reference
page
Error code Red LED Red LED
Green
LED (1)
No-indication Stays OFF
Stays OFF
Keeps
flashing
—
• Normal operation
—
—
Stays OFF Stays OFF
Indoor unit power supply
• Power OFF, broken wire/blown fuse, broken transformer wire
Repair
112
*
3-time
flash
Keeps
flashing
Remote control wires
• Poor connection, breakage of remote control wire * For wire breaking at power ON, the LED is OFF.
Repair
113
Remote control
• Defective remote control PCB
Replacement of
remote control
WAIT
or
INSPECT I/U
Stays OFF
Keeps
flashing
Indoor-outdoor units connection
wire
• Poor connection, breakage of indoor-outdoor units connection wire
Repair
114
~
119
Remote control
• Improper setting of master and slave by remote control
Keeps
flashing
Stays OFF
*
Keeps
flashing
Remote control wires (Noise)
•
Poor connection of remote control signal wire (White)
•
Intrusion of noise in remote control wire
* For wire breaking at power ON, the LED is OFF
Repair
120
Remote control indoor control
PCB
*
• Defective remote control or indoor control PCB (defective communication circuit)?
Replacement of
remote control or
PCB
2-time
flash
Keeps
flashing
Indoor-outdoor units connection
wire
•
Poor connection of wire between indoor-outdoor units during operation
(disconnection, loose connection)
•
Anomalous communication between indoor-outdoor units by noise, etc.
Repair
121
2-time
flash
Keeps
flashing
(Noise)
•
CPU-runaway on outdoor control PCB
Power reset or
Repair
Outdoor control PCB
*
• Occurrence of defective outdoor control PCB on the way of power supply (defective communication
circuit)?
Replacement of
PCB
2-time
flash
Keeps
flashing
Outdoor control PCB
•
Defective outdoor control PCB on the way of power supply
Replacement
Fuse
•
Blown fuse
1-time flash
Keeps
flashing
Indoor heat exchanger tempera-
ture thermistor
•
Defective indoor heat exchanger temperature thermistor
(defective element, broken wire,
short-circuit)
• Poor contact of temperature thermistor connector
Replacement, repair
of temperature
thermistor
122
Indoor control PCB
*
•
Defective indoor control PCB (Defective temperature thermistor input circuit)?
Replacement of
PCB
1-time flash
Keeps
flashing
Indoor return air temperature
thermistor
•
Defective indoor return air temperature thermistor
(defective element, broken wire, short-circuit)
• Poor contact of temperature thermistor connector
Replacement, repair
of temperature
thermistor
123
Indoor control PCB
*
•
Defective indoor control PCB (Defective temperature thermistor input circuit)?
Replacement of
PCB
1-time flash
Keeps
flashing
Installation or operating condi-
tion
•
Heating over-load
(Anomalously high indoor heat exchanger temperature)
Repair
124
Indoor heat exchanger tempera-
ture thermistor
•
Defective indoor heat exchanger temperature thermistor (short-circuit)
Replacement of
temperature therm-
istor
Indoor control PCB
*
•
Defective indoor control PCB
(Defective temperature thermistor input circuit)?
Replacement of
PCB
1-time flash
Keeps
flashing
Drain trouble
•
Defective drain pump (DM), broken drain pump wire
, disconnected connector
Replacement, repair
of DM
125
Float switch
•
Anomalous float switch operation
(malfunction)
Repair
Indoor control PCB
*
•
Defective indoor control PCB
(Defective float switch input circuit)
*
•
Defective indoor control PCB
(Defective DM drive output circuit)?
Replacement of
PCB
Option
•
Defective optional parts
(At optional anomalous input setting)
Repair
Stays OFF
Keeps
flashing
Number of connected indoor
units
•
When multi-unit control by remote control is performed, the number of units is over
Repair
126
1-time flash
Keeps
flashing
Fan motor
•
Defective fan motor
Replacement, repair
127
Indoor control PCB
•
Defective indoor control PCB
Replacement
1-time flash
Keeps
flashing
Indoor control PCB
•
Improper operation mode setting
Repair
128
1-time flash
Keeps
flashing
Fan motor
•
Indoor fan motor rotation speed anomaly
Replacement, repair
129
Indoor control PCB
•
Defective indoor control PCB
Replacement
Stays OFF
Keeps
flashing
Remote control temperature
thermistor
• Broken wire of remote control temperature thermistor
Repair
130
Note (1)
Normal indicator lamp (Indoor unit: Green) extinguishes (or lights continuously) only when CPU is anomalous. It keeps flashing
in any trouble other than anomalous CPU.
(2) * mark in the description of trouble means that, in ordinary diagnosis, it cannot identify the cause definitely, and, if the trouble is repaired by replacing
the part, it is judged consequently that the replaced part was defective.
Содержание SRR25ZJ-S
Страница 30: ... 29 14 SR T 157 2 4way ceiling cassette type FDTC Models FDTC25VF 35VF 35 ...
Страница 34: ... 33 14 SR T 157 See page 29 a PJA012D783 ...
Страница 86: ... 85 14 SR T 157 09 SRK DB 087D Service data record form 78 ...
Страница 164: ... 163 14 SR T 157 5 Super link E board SC ADNA E F SL2NA E and SL3N AE BE to control 5 Super link E board SC ADNA E ...
Страница 165: ... 164 14 SR T 157 ...