'14 • SR-T-157
Air flow
outdoor
air temp.
indoor air temp
16˚CDB
18˚CDB
20˚CDB
22˚CDB
24˚CDB
Hi
11.0
(m
3
/min)
-15˚CWB
2.58
2.53
2.47
2.42
2.36
-10˚CWB
2.92
2.87
2.83
2.76
2.70
-5˚CWB
3.17
3.12
3.06
3.02
2.97
0˚CWB
3.32
3.27
3.21
3.18
3.13
5˚CWB
4.23
4.18
4.16
4.07
4.02
6˚CWB
4.30
4.25
4.20
4.15
4.10
10˚CWB
4.57
4.52
4.49
4.43
4.39
15˚CWB
4.97
4.93
4.89
4.84
4.79
20˚CWB
5.34
5.30
5.27
5.21
5.17
Model SRR35ZJ-S
Cooling Mode
Model SRR25ZJ-S
Cooling Mode
Air flow
outdoor
air temp.
indoor air temp
16˚CDB
18˚CDB
20˚CDB
22˚CDB
24˚CDB
Hi
10.0
(m
3
/min)
-15˚CWB
2.09
2.05
2.00
1.96
1.91
-10˚CWB
2.37
2.33
2.29
2.24
2.19
-5˚CWB
2.56
2.53
2.48
2.45
2.41
0˚CWB
2.69
2.65
2.60
2.57
2.53
5˚CWB
3.42
3.38
3.37
3.30
3.25
6˚CWB
3.48
3.44
3.40
3.36
3.32
10˚CWB
3.70
3.66
3.64
3.59
3.55
15˚CWB
4.02
3.99
3.96
3.92
3.88
20˚CWB
4.32
4.29
4.27
4.22
4.19
Air flow
Outdoor
air temp.
Indoor air temp
21˚CDB
23˚CDB
26˚CDB
27˚CDB
28˚CDB
31˚CDB
33˚CDB
14˚CWB
16˚CWB
18˚CWB
19˚CWB
20˚CWB
22˚CWB
24˚CWB
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
Hi
8.5
(m
3
/min)
10
2.82 2.25 2.95 2.21 3.06 2.29 3.11 2.27 3.16 2.24 3.26 2.31 3.34 2.24
12
2.77 2.22 2.90 2.18 3.01 2.28 3.07 2.25 3.12 2.22 3.22 2.30 3.31 2.23
14
2.71 2.19 2.85 2.16 2.97 2.26 3.03 2.23 3.08 2.21 3.18 2.28 3.28 2.22
16
2.66 2.17 2.80 2.14 2.92 2.24 2.98 2.22 3.04 2.19 3.15 2.27 3.24 2.21
18
2.60 2.14 2.74 2.12 2.88 2.22 2.94 2.20 2.99 2.17 3.11 2.26 3.20 2.20
20
2.55 2.11 2.68 2.09 2.83 2.19 2.89 2.18 2.95 2.14 3.07 2.24 3.17 2.18
22
2.49 2.09 2.63 2.06 2.78 2.17 2.84 2.15 2.90 2.13 3.02 2.23 3.13 2.17
24
2.43 2.06 2.57 2.03 2.72 2.15 2.80 2.13 2.85 2.11 2.98 2.21 3.08 2.16
26
2.37 2.03 2.51 2.01 2.67 2.13 2.74 2.11 2.80 2.09 2.93 2.19 3.04 2.14
28
2.31 2.00 2.44 1.98 2.61 2.11 2.69 2.10 2.75 2.08 2.89 2.18 3.00 2.11
30
2.24 1.97 2.38 1.95 2.56 2.08 2.64 2.08 2.70 2.05 2.84 2.16 2.95 2.10
32
2.18 1.94 2.31 1.92 2.50 2.06 2.58 2.05 2.64 2.03 2.79 2.13 2.90 2.09
34
2.11 1.90 2.25 1.89 2.44 2.03 2.53 2.03 2.59 2.01 2.74 2.11 2.85 2.07
35
2.08 1.89 2.21 1.87 2.41 2.02 2.50 2.02 2.56 2.00 2.71 2.11 2.83 2.07
36
2.04 1.87 2.18 1.86 2.38 2.01 2.47 2.01 2.53 1.99 2.69 2.10 2.80 2.06
38
1.97 1.84 2.11 1.83 2.32 1.98 2.41 1.98 2.47 1.97 2.63 2.08 2.75 2.04
39
1.94 1.82 2.07 1.81 2.28 1.97 2.38 1.97 2.44 1.96 2.61 2.07 2.72 2.04
Air flow
Outdoor
air temp.
Indoor air temp
21˚CDB
23˚CDB
26˚CDB
27˚CDB
28˚CDB
31˚CDB
33˚CDB
14˚CWB
16˚CWB
18˚CWB
19˚CWB
20˚CWB
22˚CWB
24˚CWB
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
Hi
9.0
(m
3
/min)
10
3.94 2.93 4.13 2.87 4.28 2.95 4.35 2.91 4.43 2.87 4.56 2.93 4.68 2.83
12
3.87 2.89 4.06 2.84 4.22 2.93 4.29 2.89 4.37 2.85 4.51 2.91 4.63 2.82
14
3.80 2.85 3.99 2.80 4.16 2.90 4.24 2.86 4.31 2.81 4.46 2.89 4.59 2.80
16
3.72 2.81 3.91 2.76 4.09 2.86 4.18 2.82 4.25 2.79 4.40 2.87 4.54 2.78
18
3.65 2.77 3.84 2.73 4.03 2.83 4.11 2.80 4.19 2.77 4.35 2.84 4.49 2.76
20
3.57 2.72 3.76 2.69 3.96 2.80 4.05 2.77 4.13 2.74 4.29 2.82 4.43 2.74
22
3.49 2.68 3.68 2.64 3.89 2.77 3.98 2.74 4.06 2.71 4.23 2.80 4.38 2.72
24
3.40 2.64 3.59 2.61 3.81 2.73 3.91 2.71 3.99 2.68 4.17 2.77 4.32 2.70
26
3.32 2.59 3.51 2.57 3.74 2.70 3.84 2.69 3.92 2.65 4.11 2.75 4.26 2.68
28
3.23 2.55 3.42 2.52 3.66 2.66 3.77 2.65 3.85 2.63 4.04 2.73 4.20 2.66
30
3.14 2.50 3.33 2.48 3.58 2.63 3.70 2.62 3.78 2.59 3.98 2.70 4.13 2.62
32
3.05 2.45 3.24 2.44 3.50 2.60 3.62 2.59 3.70 2.56 3.91 2.66 4.06 2.60
34
2.95 2.41 3.14 2.39 3.41 2.56 3.54 2.55 3.62 2.53 3.84 2.64 4.00 2.58
35
2.91 2.38 3.10 2.37 3.37 2.54 3.50 2.54 3.58 2.51 3.80 2.63 3.96 2.57
36
2.86 2.36 3.05 2.35 3.33 2.52 3.46 2.52 3.54 2.49 3.76 2.61 3.92 2.56
38
2.76 2.31 2.95 2.30 3.24 2.47 3.38 2.49 3.46 2.46 3.69 2.59 3.85 2.54
39
2.71 2.29 2.90 2.28 3.20 2.46 3.33 2.46 3.42 2.44 3.65 2.58 3.81 2.53
(1) Ceiling concealed type (SRR)
Note(1) These data show average statuses.
Depending on the system control, there may be ranges where the operation is
not conducted continuously.
These data show the case where the operation frequency of a compressor is
fixed.
(2) Capacities are based on the following conditions.
Corresponding refrigerant piping length :7m
Level difference of Zero.
(3) Symbols are as follows.
TC : Total cooling capacity (kW)
SHC : Sensible heat capacity (kW)
HC : Heating capacity (kW)
Heating Mode (HC)
(kW)
(kW)
Heating Mode (HC)
(kW)
(kW)
7. CAPACITY TABLES
Содержание SRR25ZJ-S
Страница 30: ... 29 14 SR T 157 2 4way ceiling cassette type FDTC Models FDTC25VF 35VF 35 ...
Страница 34: ... 33 14 SR T 157 See page 29 a PJA012D783 ...
Страница 86: ... 85 14 SR T 157 09 SRK DB 087D Service data record form 78 ...
Страница 164: ... 163 14 SR T 157 5 Super link E board SC ADNA E F SL2NA E and SL3N AE BE to control 5 Super link E board SC ADNA E ...
Страница 165: ... 164 14 SR T 157 ...