118
-
'14 • SR-T-157
WAIT
Communication error at
initial operation (2/3)
1. Applicable model
5. Troubleshooting
All models
When the fuse is blown, the
method to inspect outdoor PCB
before replacing the power
supply fuse
Diagnosis
Countermeasure
Replace the outdoor
PCB
YES
YES
NO
YES
Replace the outdoor
control PCB
NO
Replace the
reactor.
NO
Isn’t there
a short-circuit between phases of
outdoor PCB?
Aren’t there
cracks or burning on the power
ransistor module or diode
stack?
Isn’t reactor the anomalous?
From previous page
Replace fuse.
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
• Blown fuse
• Faulty outdoor PCB
• Faulty reactor
Note:
Error code
Remote control:
LED
Green
Red
Indoor
Stays OFF
Keeps flashing
Content