119
-
'14 • SR-T-157
WAIT
Communication error at
initial operation (3/3)
1. Applicable model
5. Troubleshooting
All models
When the remote control
display is extinguished after the
power on.
Diagnosis
Countermeasure
YES
NO
Remote control display is
extinguished after the power on.
YES
NO
NO
YES
NO
YES
Is the
green LED on the indoor unit
flashing?
Is the
fuse on the indoor control
PCB OK?
Is
approx. DC 10-11V detected
between wires at the remote control
side after disconnecting the
remote control?
Are wires
connected properly between the indoor and
the outdoor units?
Is approx.
DC20V detected between
�
-
�
on the outdoor unit terminal
block?
NO
YES
Is approx
DC20V detected between
�
-
�
on the indoor unit terminal
block?
YES
NO
NO
Replace fuse.
Short-circuit on remote
control wire
Defective remote control
Correct wires.
Defective outdoor
PCB
➞
Replace.
Defective connection wire
(Broken wire)
Noise
Defective indoor control
PCB
➞
Replace.
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
• Blown fuse
• Connection between PCB’s
• Blown fuse
• Faulty indoor control PCB
• Defective remote control
• Wire breakage on remote
control
• Faulty outdoor PCB
Note:
Error code
Remote control:
LED
Green
Red
Indoor
Stays OFF
Keeps flashing
Content
Содержание SRR25ZJ-S
Страница 30: ... 29 14 SR T 157 2 4way ceiling cassette type FDTC Models FDTC25VF 35VF 35 ...
Страница 34: ... 33 14 SR T 157 See page 29 a PJA012D783 ...
Страница 86: ... 85 14 SR T 157 09 SRK DB 087D Service data record form 78 ...
Страница 164: ... 163 14 SR T 157 5 Super link E board SC ADNA E F SL2NA E and SL3N AE BE to control 5 Super link E board SC ADNA E ...
Страница 165: ... 164 14 SR T 157 ...