'14 • SR-T-157
None
Louver motor failure
Keeps flashing
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
YES
Is LM wiring
broken?
Is LM locked?
�
Check at the indoor unit side.
LM: louver motor
Is the louver
operable with the remote
control?
YES
NO
Does the louver
operate at the power
on?
YES
NO
YES
NO
Operate after
waiting for more
than 1 minute.
Repair wiring.
Defective indoor control
PCB
➞
Replace.
Replace LM.
Normal
Adjust LM lever and then
check again.
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
• Defective LM
• LM wire breakage
• Faulty indoor control PCB
Note:
Error code
Remote control:
LED
Green
Red
Indoor
Content