58
-
'14 • SR-T-157
(a) Auto operation
If “Auto” mode is selected by the remote control, the heating and the cooling are automatically switched according to
the difference between outdoor air temperature and setting temperature and the difference between setting temperature
and return air temperature. (When the switching of cooling mode
↔
heating mode takes place within 3 minutes, the
compressor does not operate for 3 minutes by the control of 3-minute timer.) This will facilitate the cooling/heating
switching operation in intermediate seasons and the adaptation to unmanned operation at stores, etc (ATM corner of
bank).
(b) Operations of functional items during cooling/heating
Cooling
Heating
Dehumidify
Fan
Operation
Functional item
Thermostat
ON
Thermostat
ON
Thermostat
OFF
Thermostat
OFF
Hot start
(Defrost)
Compressor
4-way valve
Outdoor unit fan
Indoor unit fan
Louver motor
Drain pump
(3)
�
�
�
�
�
�
�
�
�
�
(2)
�
�
�
�
�
(2)
�
�
�
�
/
�
�
/
�
�
�
�
�
/
�
�
/×
�
�
(
�
)
�
(
�
)
�
/
�
�
/
�
�
/
�
�
�
/
�
�
/
�
�
/
�
Thermostat ON:
�
Thermostat OFF:
�
(2)
�
/
�
�
/
�
(2)
Note (1)
�
:
Operation
�
: Stop
�
/
�
: Turned ON/OFF by the control other than the room temperature control.
(2) ON during the drain motor delay control.
(3) Drain pump ON setting may be selected with the indoor unit function setting of the wired remote control.
(c) Dehumidifying operation
Return air temperature thermistor [ThI-A (by the remote control when the remote control thermistor is enabled)]
controls the indoor temperature environment simultaneously.
(i)
Operation is started in the cooling mode. When the difference between the return air temperature and the
setting temperature is 2°C or less, the indoor unit fan tap is brought down by one tap. That tap is retained for
3 minutes after
changing the indoor unit fan tap.
(ii) If the return air temperature exceeds the setting temperature by 3°C during defrosting operation, the indoor
unit fan tap is raised. That tap is retained for 3 minutes after changing the indoor unit fan tap.
(iii)
If the thermostat OFF is established during the above control, the indoor unit fan tap at the thermostat ON is
retained so far as the thermostat is turned OFF.
(iv)
After stopping the cooling operation, the indoor unit continues to run at Lo for 15 seconds.
(d) Timer operation
(i) Sleep timer
Set the duration of time from the present to the time to turn off the air-conditioner.
It can be selected from 10 steps in the range from “OFF 1 hour later” to “OFF 10 hours later”. After the sleep timer
setting, the remaining time is displayed with progress of time in the unit of hour.
(ii) OFF timer
Time to turn OFF the air-conditioner can be set in the unit of 10 minutes.
(iii) ON timer
Time to turn ON the air-conditioner can be set. Indoor temperature can be set simultaneously.
(iv) Weekly timer
Timer operation (ON timer, OFF timer) can be set up to 4 times a day for each weekday.
Note (1) Room temperature control during auto cooling/auto heating is performed according to the room temperature setting temperature. (DIFF: ±1 deg)
Room temperature setting temperature
+3
-3
Cooling operation
Heating operation
Room temperature (detected with ThI-A) [deg]
(3) Operation control function by the indoor control
Содержание SRR25ZJ-S
Страница 30: ... 29 14 SR T 157 2 4way ceiling cassette type FDTC Models FDTC25VF 35VF 35 ...
Страница 34: ... 33 14 SR T 157 See page 29 a PJA012D783 ...
Страница 86: ... 85 14 SR T 157 09 SRK DB 087D Service data record form 78 ...
Страница 164: ... 163 14 SR T 157 5 Super link E board SC ADNA E F SL2NA E and SL3N AE BE to control 5 Super link E board SC ADNA E ...
Страница 165: ... 164 14 SR T 157 ...