121
-
'14 • SR-T-157
E5
Communication error during operation
Keeps flashing
2-
time flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Has the remote
control LCD returned to
normal state?
YES
NO
Is the
connection of signal
wires at the outdoor unit
side OK?
Is the
connection of signal
wires between indoor-outdoor
units OK?
Note (1) Inspect faulty connections (disconnection,
looseness) on the outdoor unit terminal block.
Power reset
Note (2) Check for faulty connection or breakage of
signal wires between indoor-outdoor units.
YES
NO
YES
NO
Repair signal wires.
Repair signal wires.
Defective outdoor PCB
(Defective network
communication circuit)
➞
Replace.
Unit is normal.
(Malfunction by temporary
noise, etc.)
2. Error detection method
When normal communication
between indoor and outdoor
unit is interrupted for more than
2 minutes.
3. Condition of Error displayed
Same as above is detected
during operation.
4. Presumable cause
• Unit No. setting error
• Broken remote control wire
• Faulty remote control wire
connection
• Faulty outdoor PCB
Note:
Error code
Remote control:
LED
Green
Red
Indoor
Content
Содержание SRR25ZJ-S
Страница 30: ... 29 14 SR T 157 2 4way ceiling cassette type FDTC Models FDTC25VF 35VF 35 ...
Страница 34: ... 33 14 SR T 157 See page 29 a PJA012D783 ...
Страница 86: ... 85 14 SR T 157 09 SRK DB 087D Service data record form 78 ...
Страница 164: ... 163 14 SR T 157 5 Super link E board SC ADNA E F SL2NA E and SL3N AE BE to control 5 Super link E board SC ADNA E ...
Страница 165: ... 164 14 SR T 157 ...