140
-
'14 • SR-T-157
Error code
Remote controller: E51
LED
Green
Red
Indoor
Content
Power transistor error
Keeps flashing Stays Off
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
2. Error detection method
3.Condition of Error displayed
4. Presumable cause
Note:
If the power transistor primary
current exceeds the setting value
for 3 seconds, the compressor
stops.
Power transistor primary current
• Faulty outdoor PCB
• Dust on control PCB
• Blown F2 fuse
NO
NO
YES
Check soldered
surfaces on the outdoor control PCB for
foreign matter like dust,
fouling,etc.
Isn
’t F2 fuse
(AC250V, 20A)blown?
Remove foreign matter
like dust, fouling, etc.
Replace fuse.
Defective outdoor
PCB
ª
Replace.
YES
Error code
Remote control:
LED
Green
Red
Content
Indoor Keeps flashing Stays OFF
E51
Power transistor anomaly
Содержание SRR25ZJ-S
Страница 30: ... 29 14 SR T 157 2 4way ceiling cassette type FDTC Models FDTC25VF 35VF 35 ...
Страница 34: ... 33 14 SR T 157 See page 29 a PJA012D783 ...
Страница 86: ... 85 14 SR T 157 09 SRK DB 087D Service data record form 78 ...
Страница 164: ... 163 14 SR T 157 5 Super link E board SC ADNA E F SL2NA E and SL3N AE BE to control 5 Super link E board SC ADNA E ...
Страница 165: ... 164 14 SR T 157 ...