136
-
'14 • SR-T-157
E42
Current cut (1/2)
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is the
Power supply
voltage OK?
YES
Are the
service valves
opened?
NO
To next page.
YES
Is the
high pressure
during operation
OK?
YES
Is the
checked result of
insulation resistance and
coil resistance (1) of
compressor motor
OK?
YES
(1) 1.703
Ω
(U-V, V-W, U-W) or more at 20°C
NO
NO
NO
Check power supply.
Open the valves.
Check refrigerant amount
and refregerant circuit
* In case of transitional
increase of high pressure
and/or test run, several
times restarting may
recover it, because liquid
refrigerant (migrated)
in the compresser is
discharged from the
compressor.
Replace compressor.
2. Error detection method
In order to prevent from
overcurrent of inverter,
if the current exceeds the
specifications, it makes the
compressor stopping.
3. Condition of Error displayed
• If the output current of inveter
exceeds the specifications,
it makes the compressor
stopping.
4. Presumable cause
• The valves closed
• Faulty power supply
• Insufficient refrigerant amount
• Faulty compressor
• Faulty power transistor
module
Note:
Error code
Remote control:
LED
Green
Red
Content
Indoor Keeps flashing Stays OFF
Содержание SRR25ZJ-S
Страница 30: ... 29 14 SR T 157 2 4way ceiling cassette type FDTC Models FDTC25VF 35VF 35 ...
Страница 34: ... 33 14 SR T 157 See page 29 a PJA012D783 ...
Страница 86: ... 85 14 SR T 157 09 SRK DB 087D Service data record form 78 ...
Страница 164: ... 163 14 SR T 157 5 Super link E board SC ADNA E F SL2NA E and SL3N AE BE to control 5 Super link E board SC ADNA E ...
Страница 165: ... 164 14 SR T 157 ...