50
-
'14 • SR-T-157
(a) Frost prevention control
(During cooling or dehumidifying)
(i) Operating conditions
1) Indoor heat exchanger temperature (Th2) is lower than 5ºC.
2) 5 minutes after reaching the compressor command speed except 0 rps.
(ii) Detail of anti-frost operation
(iii) Reset conditions:
When either of the following condition is satisfied.
1)
The indoor heat exchanger temperature (Th2) is 8ºC or higher.
2)
The compressor command speed is 0 rps.
(b) Cooling overload protective control
(i) Operating conditions:
When the outdoor air temperature (TH2) has become continuously for 30 seconds
at 41ºC or more, or 47ºC or more with the compressor running, the lower limit
speed of compressor is brought up.
(ii) Detail of operation
1) The outdoor fan is stepped up by 3 speed step. (Upper limit 7th speed.)
2) The lower limit of compressor command speed is set to 30 or 40 rps and even if the calculated result be-
comes lower than that after fuzzy calculation, the speed is kept to 30 or 40 rps. However, when the thermo
OFF, the speed is reduced to 0 rps.
(iii) Reset conditions:
When either of the following condition is satisfied.
1)
The outdoor air temperature is lower than 40ºC.
2)
The compressor command speed is 0 rps.
(13) Protective control function
Item
5°C or lower
2.5°C or lower
Lower limit of compressor command speed
22 rps
0 rps
Indoor fan
Depends on operation mode
Protects the fan tap just before
frost prevention control
Outdoor fan
Depends on command speed
Depends on stop mode
4-way valve
OFF
Indoor heat exchanger
temperature (ºC)
2.5
5
8
0 rps
Lower
limit
speed
compressor
command
speed
Notes (1) When the indoor heat exchanger temperature is in the range of 2.5~5 ºC, the speed is reduced by 4 rps at each 20 seconds.
(2) When the temperature is lower than 2.5 ºC, the compressor is stopped.
(3) When the indoor heat exchanger temperature is in the range of 5~8 ºC, the compressor command speed is been maintained.
Indoor heat exchanger
temperature
Model
Item
SRR25, 35ZJ-S
Outdoor air temperature
41°C or more
47°C or more
Lower limit speed
30 rps
40 rps
(c) Cooling high pressure control
(i) Purpose:
Prevents anomalous high pressure operation during cooling.
(ii) Detector:
Outdoor heat exchanger sensor (TH1)
(iii) Detail of operation:
53
58
63
Outdoor unit heat exchanger temperature (°C)
6rps
(1)
6rps
(1)
0rps
After lapse of 30 sec. or over
(3)
After lapse of 30 sec. or over
(3)
After lapse of 30 sec. or over
(3)
lower limit
speed 30 rps
(Example) Fuzzy
Notes (1) When the outdoor heat exchanger temperature is in the range of 58~63 ºC, the speed is reduced by 6 rps at each 30 seconds.
(2) When the temperature is 63 ºC or higher, the compressor is stopped.
(3) When the outdoor heat exchanger temperature is in the range of 53~58 ºC, if the compressor command speed is been maintained and
the operation has continued for more than 30 seconds at the same speed, it returns to the normal cooling operation.
(c) Cooling overload protective control
(i) Operating conditions:
(ii) Detail of operation
(iii) Reset conditions:
Item
SRF25
㨪
50ZJX-S
Outdoor air temperature
Lower limit speed
Model
40
41
46
47
1((
10
10
Outdoor air temperature ( )
C
º
1)
2)
1)
2)
The outdoor fan is stepped up by 3 speed step. (Upper limit 7th speed.)
=
model SRF25, 35 only
?
Содержание SRR25ZJ-S
Страница 30: ... 29 14 SR T 157 2 4way ceiling cassette type FDTC Models FDTC25VF 35VF 35 ...
Страница 34: ... 33 14 SR T 157 See page 29 a PJA012D783 ...
Страница 86: ... 85 14 SR T 157 09 SRK DB 087D Service data record form 78 ...
Страница 164: ... 163 14 SR T 157 5 Super link E board SC ADNA E F SL2NA E and SL3N AE BE to control 5 Super link E board SC ADNA E ...
Страница 165: ... 164 14 SR T 157 ...