120
-
'14 • SR-T-157
E1
Remote control
communication circuit error
Keeps flashing
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is it possible to
reset normally by the
power reset?
Does the drain
pump restart automatically
1 minute later?
Turn SW7-1 to OFF.
�
ON
Remove the wire
�
connecting
between indoor/outdoor units.
YES
YES
NO
Note (2) Does the remote control still display “ ” even
after 3 minutes?
Power reset
NO
WAIT
Malfunction by noise
Check peripheral
environment.
Defective indoor control
PCB
➞
Replace.
Defective remote control
➞
Replace.
2. Error detection method
When normal communication
between the remote control
and the indoor unit is
interrupted for more than 2
minutes. (Detectable only with
the remote control)
3. Condition of Error displayed
Same as above
4. Presumable cause
• Defective communication
circuit between remote
control-indoor unit
• Noise
• Defective remote control
• Faulty indoor control PCB
Note:
If the indoor unit cannot communicate normally with the remote control for 180 seconds, the indoor unit PCB starts to reset
automatically.
Error code
Remote control:
LED
Green
Red
Indoor
Content
Содержание SRR25ZJ-S
Страница 30: ... 29 14 SR T 157 2 4way ceiling cassette type FDTC Models FDTC25VF 35VF 35 ...
Страница 34: ... 33 14 SR T 157 See page 29 a PJA012D783 ...
Страница 86: ... 85 14 SR T 157 09 SRK DB 087D Service data record form 78 ...
Страница 164: ... 163 14 SR T 157 5 Super link E board SC ADNA E F SL2NA E and SL3N AE BE to control 5 Super link E board SC ADNA E ...
Страница 165: ... 164 14 SR T 157 ...