Chapter 9
233
Logic programming – Function blocks
Parameters of the function block
Parameter
Possible values
Overrun cam input
With
Without
BDC input
With
Without
Number of BDC signals per cycle
1 (e.g. eccentric press)
0-2 (e.g. hydraulic press)
Min. reset pulse time
100
ms
350
ms
Reset input
With
Without
Disable monitoring input
With
Without
Use fault present
With
Without
Enable output
The
Enable
output is used to stop the press and is connected to another
complementary press function block, e.g. Press setup or Press single stroke. If no
error was detected, the
Enable
output is High.
If any error in the contact signal sequence is detected, the
Enable
output changes to
Low, the corresponding error output changes to High and the
Reset required
output
changes to High. A valid reset sequence at the
Reset
input is then required.
The
Enable
output also changes to Low if Monitoring gets disabled.
Reset input
A valid reset sequence at the
Reset
input is a Low-High-Low transition with a
minimum pulse duration of 100 ms or 350 ms and maximum 30 s. Shorter and longer
pulses are ignored.
Ensure that the transitions of the signals for resetting fulfill the requirements of
the safety standards and regulations!
In case of a short-circuit to High (to 24 V DC) at a physical input, the evaluated signal
can have a pulse when the signal is reset due to the short-circuit detection. If such a
pulse can result in a dangerous state in the machine, the following points have to be
observed:
Ensure protected cable laying for the signal line (due to cross-circuiting to other
signal lines).
No short-circuit detection, i.e. do not reference to test outputs.
Safety-relevant signals have to conform to standards and regulations to be
applied!
Always take the valid national, regional and local regulations and standards into
consideration for your application. Type C standards such as EN 692 and EN 693
contain requirements how safety-relevant signals have to be used. For example, the
restart signal may have to be protected by suitable means in case of overrun errors
(e.g. by a key switch or in a closed control cabinet).
Table 108:
Parameters of the Universal
press contact function block
ATTENTION
Содержание SW1DNN-WS0ADR-B
Страница 2: ......
Страница 287: ...Chapter 15 284 Annex 15 Annex 15 1 Example application reports 15 1 1 Example application Newspaper palletizer ...
Страница 288: ...Chapter 15 285 Annex ...
Страница 289: ...Chapter 15 286 Annex ...
Страница 290: ...Chapter 15 287 Annex ...
Страница 291: ...Chapter 15 288 Annex ...
Страница 292: ...Chapter 15 289 Annex ...
Страница 293: ...Chapter 15 290 Annex ...
Страница 294: ...Chapter 15 291 Annex ...
Страница 295: ...Chapter 15 292 Annex ...
Страница 296: ...Chapter 15 293 Annex ...
Страница 297: ...Chapter 15 294 Annex ...
Страница 298: ...Chapter 15 295 Annex 15 1 2 Example application Wood scanner ...
Страница 299: ...Chapter 15 296 Annex ...
Страница 300: ...Chapter 15 297 Annex ...
Страница 301: ...Chapter 15 298 Annex ...
Страница 302: ...Chapter 15 299 Annex ...
Страница 303: ...Chapter 15 300 Annex ...
Страница 304: ...Chapter 15 301 Annex ...
Страница 305: ...Chapter 15 302 Annex ...
Страница 306: ...Chapter 15 303 Annex ...
Страница 307: ...Chapter 15 304 Annex 15 1 3 Example application Ramp down detection ...
Страница 308: ...Chapter 15 305 Annex ...
Страница 309: ...Chapter 15 306 Annex ...
Страница 310: ...Chapter 15 307 Annex ...
Страница 311: ...Chapter 15 308 Annex ...
Страница 312: ...Chapter 15 309 Annex ...
Страница 313: ...Chapter 15 310 Annex ...
Страница 314: ...Chapter 15 311 Annex ...
Страница 316: ...Chapter 15 313 Annex 15 3 Precautions 1 Edit a CSV file exported from Setting and Monitoring tool in a text editor ...
Страница 321: ......